WAGO-I/O-SYSTEM 750
Appendix 355
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
15.1.3.4 3-Phase Power Measurement Module
750-493
The above Analog Input Modules have a total of 9 bytes of user data in both the
Input and Output Process Image (6 bytes of data and 3 bytes of control/status).
The following tables illustrate the Input and Output Process Image, which has a
total of 6 words mapped into each image.
Word alignment is applied.
Table 263: 3-Phase Power Measurement Module
Input Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
-
S0
Status byte 0
1
D1
D0
Input data word 1
2
-
S1
Status byte 1
3
D3
D2
Input data word 2
4
-
S2
Status byte 2
5
D5
D4
Input data word 3
Output Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
-
C0
Control byte 0
1
D1
D0
Output data word 1
2
-
C1
Control byte 1
3
D3
D2
Output data word 2
4
-
C2
Control byte 2
5
D5
D4
Output data word 3
15.1.3.5 8 Channel Analog Input Modules
750-451
Table 264: 8 Channel Analog Input Modules
Input Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
D1
D0
Measured Value Channel 1
1
D3
D2
Measured Value Channel 2
2
D5
D4
Measured Value Channel 3
3
D7
D6
Measured Value Channel 4
4
D9
D8
Measured Value Channel 5
5
D11
D10
Measured Value Channel 6
6
D13
D12
Measured Value Channel 7
7
D15
D14
Measured Value Channel 8