98 Commissioning
WAGO-I/O-SYSTEM 750
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
7.8.1
Configuration via Web-Based-Management (WBM)
The HTML pages (from here on referred to as “pages”) of the Web-Based
Management are used to configure the controller. Proceed as follows to access
the WBM using an Internet browser:
1.
Connect the controller to the ETHERNET network via the ETHERNET
interface X1.
2.
To access the pages, enter “https://” followed by the controller's IP address
and “/wbm” in the address line of your browser, e.g.,
“https://192.168.1.17/wbm.”
Note that the PC and the controller must be located within the same subnet
(see Section “Setting an IP Address”). If you do not know the IP address
and cannot determine it, switch the controller to the pre-set address
“192.168.1.17” using the “Fixed IP address” function (see Section “Initiate
Reset Functions” > “Set Fixed IP Address”).
If you have installed a DHCP server on your PC and would like to access WBM
through DHCP, use the other interface. You can find detailed information about
this in the section “Assigning an IP Address Using DHCP.”
Displaying the Controller Start Page
If the controller does not display the start page, ensure that your Internet browser
settings permit the bypassing of the proxy server for local addresses. Also check
whether your PC is located in the same subnet as the controller.
Take usage by the CODESYS program into account
If the controller is at capacity due to a CODESYS program, this may result in
slower processing in the WBM. As a result, timeout errors are sometimes
reported in some circumstances. It is therefore important to stop the CODESYS
application prior to performing complicated configurations using WBM.