Table 72: Submodule Types and Data Lenghts – Digital Output Modules
PNIO module type
Process data length [byte]/
allocation [bit]
Telegram
allocation [byte]
PNIO submodule type
Data type
Input (I-PI) Output (O-PI) Input
Output
4DO
4DO (+ 4 BIT O)
OctetString[1],
bit field
0
0
1
4
1
2
4DO (+12 BIT O)
OctetString[2],
bit field
0
0
2
4
1
3
4DO (+28 BIT O)
OctetString[4],
bit field
0
0
4
4
1
5
4DO (- 4 BIT O)
-
0
0
0
4
1
1
4DO, DIA
4DO (+ 4 BIT O), DIA OctetString[1],
bit field
0
0
1
4
1
2
4DO (+12 BIT O), DIA OctetString[2],
bit field
0
0
2
4
1
3
4DO (+28 BIT O), DIA OctetString[4],
bit field
0
0
4
4
1
5
4DO (- 4 BIT O), DIA -
0
0
0
4
1
1
4DO (+ 4 BIT I/O),
DIA in I-PI
OctetString[1],
bit field
4
4
1
4
3
3
4DO (+12 BIT I/O),
DIA in I-PI
OctetString[2],
bit field
2
4
2
4
4
4
4DO (+28 BIT I/O),
DIA in I-PI
OctetString[4],
bit field
4
4
4
4
6
6
4DO (- 4 BIT I/O),
DIA in I-PI
-
0
4
0
4
1
1
8DO
8DO
OctetString[1],
bit field
0
0
1
8
1
2
8DO (+ 8 BIT O)
OctetString[2],
bit field
0
0
2
8
1
3
8DO (+24 BIT O)
OctetString[4],
bit field
0
0
4
8
1
5
8DO (- 8 BIT O)
-
0
0
0
8
1
1