WAGO-I/O-System 750
Appendix 207
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
Table 173: Additional Error Information Error Type “Configuration Fault (0x0010)“
Fault type “Configuration fault (0x0010)“
Extended
fault type
Additional
value
Description
0x009C
0xC001809C
The integration of control and status data of complex modules
(Table 0, register 3) is activated.
0x009D
0xC001809D
Formatting of complex module data (Table 0, register 3) is not
allowed.
0x009E
0xC001809E
Formatting of digital module data (Table 0, register 3) is not
allowed.
0x009F
0xC001809F
The data allocation (Table 0, register 3) is not allowed (neither
bytes nor words).
0x00A0
0xC00180A0
The setting for updating the input data (Table 0, register 3) is not
allowed (not asynchronous).
0x00A1
0xC00180A1
The setting for updating the output data (Table 0, register 3) is
not allowed (not asynchronous).
0x00A2
0xC00180A2
The setting for the behavior of fieldbus faults (Table 0, register
3) is not allowed.
0x00A3
0xC00180A3
The setting for the behavior of internal data bus faults (Table 0,
register 3) is not allowed.
0x00A4
0xC00180A4
The setting for activating the diagnostics (Table 0, register 3) is
not allowed.
0x00A5
0xC00180A5
The linking of the diagnostic data to the process image (Table 0,
register 3) is activated.
0x00A6
0xC00180A6
The reserved station parameters (Table 0, register 4) have invalid
values.
…
…
…
0x00B2
0xC00180B2
The reserved station parameters (Table 0, register 4) have invalid
values.
0x00B3
0xC00180B3
The reserved station parameter (Table 100, register 75) have
invalid values.
0x00B4
0xC00180B4
The module setting (Table 100, register 75) is not allowed.
0x00B5
0xC00180B5
The reserved station parameter (Table 100, register 76) have
invalid values.
0x00B6
0xC00180B6
The reserved station parameter (Table 100, register 77) have
invalid values.
0x00B7
0xC00180B7
The setting for the behavior of PROFINET IO faults (stop
internal data bus) when using PROFIsafe modules is not allowed.
Missing parameters for both the station substitute (fieldbus coupler) and the
modules (I/O modules) are also reported using an extended channel diagnostics.
Fault type 0x001F is classified as missing parameters in accordance with the
standard.
Table 174: Additional Error Information Fault type “Missing Parameters 0x001F”
Fault type “Missing parameters (0x001F)”
Extended
fault type
Additional
value
Description
0x0009
0xC0018009
Module or fieldbus coupler is not configured.
Faults occurring on the internal data bus system are also indicated by transmitting
an extended channel diagnostics. This is a manufacturer specific fault that is
displayed using the fault type 100
H
. Additional fault information is available in
the following table.