162 Appendix
WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
14.1.5 Analog Output Modules
The module/submodule types are listed for the analog output modules and the
substitute I/O modules assigned in the tables below.
The subsequent tables for the submodule types and data lengths list the number of
data bytes provided in the respective process image for the individual submodules.
The respective number of bytes of the telegrams in the send and receive direction
is also specified as input IOD
IOC (provider) and output IOC
IOD
(consumer).
The group of analog output modules is divided into two module types.
Table 77: Module Types – Analog Output Modules
Module type
Description
Substitute I/O modules
2AO
2-Channel Analog Output Modules,
16 bits output data per signal channel
75x-550, 75x-552, 75x-554,
75x-556, 75x-560, 75x-562,
75x-563, 750-585, 750-586,
plus all variations
4AO
4-Channel Analog Output Modules,
16 bits output data per signal channel
75x-553, 75x-555, 75x-557,
75x-559,
plus all variations
Analog output modules receive the provider status (IOPS) from the I/O controller
and supply it with the consumer status (IOCS) of the existing output information
if only the actual user data is replaced. If all existing information is available in
the process image of the inputs and outputs, the process data qualifiers are also
transmitted in the opposite direction.
The group of analog output modules is divided into the following submodule
types.
Table 78: Submodule Types and Data Lengths – Analog Output Modules
PNIO module type
Process data length [byte]
Telegram
allocation [byte]
PNIO submodule type
Data type
Input (I-PI) Output (O-PI) Input
Output
2AO
2AA, …
Integer16
0
4
1
5
2AA, …, EM
{Unsigned8,
Integer16}
6
6
8
8
4AO
4AA, …
Integer16
0
8
1
9
4AA, …, EM
{Unsigned8,
Integer16}
12
12
14
14