206 Appendix
WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
Table 173: Additional Error Information Error Type “Configuration Fault (0x0010)“
Fault type “Configuration fault (0x0010)“
Extended
fault type
Additional
value
Description
0x0021
0xC0018021
The substitute value behavior for the output of the module is not
allowed.
0x0024
0xC0018024
The reserved output parameters of the module have an invalid
value.
0x0030
0xC0018030
The combination of input and diagnostics is not supported in the
process image.
0x0031
0xC0018031
The combination of input and diagnostics is not allowed in the
process image.
0x0032
0xC0018032
The bit offset for the output of the module is not allowed.
0x0033
0xC0018033
The bit offset for the diagnostic of the module exceeds the
maximum offset.
0x0034
0xC0018034
The reserved diagnostic parameters of the module have an
invalid value.
0x0035
0xC0018035
The diagnostic connection of the module is aborted.
0x0051
0xC001xx51
The reserved channel parameter of the module has an invalid
value.
0x0060
0xC001xx60
The substitute value for the input channel of the module is not
allowed.
0x0061
0xC001xx61
The substitute value for the input channel of the module exceeds
its maximum.
0x0062
0xC001xx62
The substitute value for the input channel of the module falls
below its minimum.
0x0070
0xC001xx70
The substitute value for the output channel of the module is not
allowed.
0x0071
0xC001xx71
The substitute value for the output channel of the module
exceeds its maximum.
0x0072
0xC001xx72
The substitute value for the output channel of the module falls
below its minimum.
0x0080
0xC001xx80
The substitute value for the output channel of the module is not
allowed.
0x0081
0xC001xx81
The connection of the channel diagnostics of the module is not
allowed.
0x0090
0xC0018090
The status of the station during the configuration is not allowed.
0x0091
0xC0018091
The length of the configuration data for the station is smaller
than expected.
0x0092
0xC0018092
The length of the configuration data for the station is larger than
expected.
0x0093
0xC0018093
The reserved station parameters (Table 0, register 0) have invalid
values.
0x0094
0xC0018094
The reserved station parameters (Table 0, register 1) have invalid
values.
0x0095
0xC0019095
The register access (Table 0, register 1) is not allowed.
0x0096
0xC0018096
The setting of the diagnostic channel (Table 0, register 1) is not
allowed.
0x0097
0xC0018097
The reserved station parameters (Table 0, register 2) have invalid
values.
0x0098
0xC0018098
The setting for the internal data bus extension (Table 0, register
2) is not allowed.
0x0099
0xC0018099
The reserved station parameters (Table 0, register 3) have invalid
values.
0x009A
0xC001809A
The connection for creating the process image (Table 0, register
3) is deactivated.
0x009B
0xC001809B
The algorithm for creating the process image (Table 0, register 3)
is not allowed.