9.2
SNMP
Pos: 71.8.2 /Serie 750 (WAGO-I/O-SYST EM)/Web-Based-Management-System WBM/Seite SNMP/SNM P - Einl eitung @ 4\mod_1242627851796_21.docx @ 33417 @ @ 1
On the HTML page “SNMP”, you can perform the settings for the Simple
Network Management Protocol.
SNMP is a standard for device management within a TCP/IP network. The Simple
Network Management Protocol (SNMP) is responsible for transporting the control
data that allows the exchange of management information, the status and statistic
data between individual network components and a management system.
Pos: 71.8.3 /Serie 750 (WAGO-I/O-SYST EM)/Web-Based-Management-System WBM/Seite SNMP/SNM P - D as Protokoll wird i n der Version 1, 2c und 3 unterstützt. @ 4\mod_1243331480234_21.docx @ 33890 @ @ 1
The fieldbus coupler/controller supports SNMP in versions 1, 2c and 3.
Pos: 71.8.4 /Serie 750 (WAGO-I/O-SYST EM)/Web-Based-Management-System WBM/Seite SNMP/SNM P - In dem F eldbuskoppler umfasst SNM P die allgemeine MIB nach RFC1213 (M IB II). ( Koppler) @ 6\mod_1264586449093_21.docx @ 48818 @ @ 1
The SNMP of the ETHERNET TCP/IP coupler includes the general MIB
according to RFC1213 (MIB II).
Pos: 71.8.5 /Serie 750 (WAGO-I/O-SYST EM)/Web-Based-Management-System WBM/Seite SNMP/SNM P - SNMP-Objekte, Z usätzlich ist ei ne spezi elle WAGO-MIB ei ngebunden. (750- 841, -871, -830) @ 6\mod_1260527822597_21.docx @ 47030 @ @ 1
In addition, a special WAGO-MIB is integrated.
Pos: 71.8.6 /Serie 750 (WAGO-I/O-SYST EM)/Web-Based-Management-System WBM/Seite SNMP/SNM P - SNMP wir d über Port 161 abgearb.; Hi nwei s: Ändern Parameter , Ver wendung (750-370) @ 23\mod_1439387867680_21.docx @ 188292 @ @ 1
SNMP is processed via port 161. The port number for SNMP traps (agent
messages) is 162.
Modify parameter via WBM or SNMP objects!
However, parameters that can be set on the html pages can also be changed
directly by the appropriate SNMP objects.
Additional Information:
Additional information for SNMP, the Management Information Base (MIB) and
traps (event messages via SNMP) may be obtained from section “Fieldbus
Communication” > … > “SNMP (Simple Network Management Protocol).”
Pos: 71.8.7 /Serie 750 (WAGO-I/O-SYST EM)/Web-Based-Management-System WBM/Seite SNMP/SNM P - Betrachten Si e die Einstellungen bezüglich SNMPv1/v2c und SNMPv3 unabhängig... (Koppl er) @ 8\mod_1279005098725_21.docx @ 59714 @ @ 1
Note that the settings for SNMPV1/V2c and SNMPV3 are separate from each
other: The different SNMP versions can be activated or used in parallel or
individually on a fieldbus coupler.