100 Commissioning
WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
8.6.4
Fail-safe Module Parameters (F-Parameter)
Fail-safe I/O modules require the standardized PROFIsafe configuration to ensure
safe exchange of production data.
Table 45: Fail-safe Module Parameters (F-Parameters)
Parameter
Setting
Description
F_Check_iPar
NoCheck
*1)
There are no individual parameters contained in the
F-parameters that have to be checked.
F_SIL
SIL3
*1)
The module complies with safety category 3.
F_CRC_Length
3-Byte-CRC
*1)
The transfer of production data transfer is
safeguarded using a 3-byte CRC in case of
PROFINET IO.
F_Par_Version
1
*1)
The version of the parameters set structure is 1.
F_Source_Add
1 … 65534
The F-Source address addresses the F-Host.
F_Dest_Add
1 … 1023 (65534
*3)
) The F-Target address addresses the F-Device.
F_WD_Time
150
*2)
50 … 10000
The F-Watchdog monitors the data exchange
between the F-Host and F-Device. The settings are
carried out in milliseconds.
F_iPar_CRC
*4)
0
*2)
… 4294967295 Signature of the individual parameter set currently
used in the module required to use the iPar server.
*1)
Fixed settings
*)
Default settings
*3)
For 75x-66x/000-003 F-Modules only by software
*4)
For 75x-66x/000-003 F-Modules only and to use the iPar server
8.6.5
General Channel Parameters
Channel properties can be set individually for a number of I/O modules. The
following channel-specific settings can be made depending on the I/O module: