WAGO-I/O-System 750
Appendix 177
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
14.2.3 Digital Output Modules with Diagnostics (DO, DIA)
If the digital output module provides diagnostic data, the following attributes can
also be set channel-by-channel during parameterization.
Table 112: Parameterization – Overview of the Additional Attributes for Digital Output Modules
with Diagnostics (DO, DIA)
Additional Attributes for the Digital Output Modules with Diagnostics (DO, DIA)
-
Diagnostics
Table 113: Parameterization DO, DIA – “Diagnostics” Attribute
Attribute name
Attribute value
Description
Diagnostics
A short circuit, line break or eternal error on the
respective signal channel:
lock (false)
•
does not lead to transmission of a diagnostic
alarm nor entry in the diagnostics database of
the station proxy.
release (true)
•
leads to transmission of a diagnostic alarm and
its entry in the diagnostics database of the
station proxy.