208 Appendix
WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
Table 175: Additional Error Information Fault Type “Internal Bus Fault 0x100“
Fault type “Internal bus fault (0x0100)“
Extended
fault type
Additional
value
Description
0x0001
0x00000106
The module configuration that has been determined on the
internal bus after AUTORESET differs from the configuration
performed before the internal bus fault occurred.
0x0003
0x01100300
Internal bus protocol fault due to internal bus RESET fault.
0x0003
0x01110300
Internal bus protocol fault due to command fault.
0x0003
0x01120300
Internal bus protocol fault due to faulty input data.
0x0003
0x01140300
Internal bus protocol fault due to faulty output data.
0x0003
0x01180300
Internal bus protocol fault caused by timeout.
0x0004
0x011204xx
Internal bus interruption after module slot xx (xx = 0 … 128).
0x0005
0x011005xx
Internal bus initializing fault because of an abortive register
communication with the module on slot xx (xx = 1 … 128).
Invalid module configurations are reported via manufacturer specific fault of type
101
H
. Additional fault information is available in the following table.
Table 176: Additional Error Information Fault Type “Configuration fault (0x0101)”
Fault type “Configuration fault (0x0101)”
Extended
fault type
Additional
value
Description
0x0012
0xC0018012
The bit offset for the inputs of the module is not allowed.
0x0013
0xC0018013
The bit offset for the inputs of the module exceed the maximum
offset.
0x0015
0xC0018015
The configured data length for the input module is smaller than
expected.
0x0016
0xC0018016
The configured data length for the input module is larger than
expected.
0x0017
0xC0018017
The configured data length for the input module is not allowed.
0x0022
0xC0018022
The bit offset for the output of the module is not allowed.
0x0023
0xC0018023
The bit offset for the output of the module exceeds the maximum
offset.
0x0025
0xC0018025
The configured data length for the output module is smaller than
expected.
0x0026
0xC0018026
The configured data length for the output module is larger than
expected.
0x0027
0xC0018027
The configured data length for the output module is not allowed.
If a fault occurs on the internal data bus system when the PNIO connection is
being established and if auto reset of the internal data bus was set by the station
proxy, then the PNIO connection must be interrupted and re-established in order
to set the parameters of the connected I/O modules. The reconfiguration request is
triggered by a manufacturer specific fault of type 102
H
. Additional fault
information is available in the following table.