204 Appendix
WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
14.5.2 Extended Channel Diagnostics
The fieldbus coupler uses the extended channel diagnostics to signal internal bus,
configuration and parameter setting faults. According to the PROFINET IO
standard, extended fault information must be expressed according to the
manufacturer specifications.
The fault type (UserstructureIdentifier) has the value for the extended channel
diagnostics (0x8002).
The structure for the data set (see ExtChannelDiagnosisData) has 12 bytes and is
composed of as follows:
Table 172: “ExtChannelDiagnosisData“ Instance Structure
Byte-
offset Date typE
Description
0 / 1
WORD
Diagnostic instance (ChannelNumber)
0x0000
…
0x000F
0x8000
Channel 0 … 15
Submodule
2 / 3
WORD
Channel-/Submodule properties (ChannelProperties)
2
7
… 2
0
Type
0x00 Instance = Submodule
0x01 1 bit
0x02 2 bit
0x03 4 bit
0x04 8 bit
0x05 16 bit
0x06 32 bit
0x07 64 bit
0x08
…
0xFF
Reserved
2
8
no collective channel error = '0'
2
10
, 2
9
Maintenance request = '00'
2
12
, 2
11
Pending diagnosis = '01'
2
15
…
2
13
Channel type
'000' Manufacturer specific
'001' Input
'010' Output
'011' Input/Output
'100'
…
'111'
reserved