Burner Setup—Gas
HI750
Continued from the previous page.
9. Conduct a smoke spot test. Follow the smoke spot tester manufacturer’s
instructions and the general guidelines below.
■
Use the access hole in the exhaust outlet.
■
Take several samples as the heater warms.
■
Take the final sample just before the heater reaches 160°F (71°C).
10.Analyze the combustion. Perform the combustion analyzer manufacturer’s
instructions and the general guidelines below.
■
Use the access hole in the exhaust outlet.
■
Take several samples as the heater warms.
■
Take the final sample just before the heater reaches 160°F (71°C).
11.Re-adjust the air setting(s) if necessary until the smoke spot test and
combustion analysis are within the following parameters:
■
O
2
content: 4–6%
■
Smoke spot: 1 or less
Result
The burner has now been set up.