ghi_tx001258gb_FM10.fm
65
HI750
Operation
Entering the burner controller diagnostic mode
The burner controller includes a diagnostic mode/function through which causes of
malfunctions may be determined. The controller sends out a sequence of pulses
which are visible on the reset button/LED display.
To enter the diagnostic mode:
1. Wait at least 10 seconds after the controller has entered the lock-out mode.
2. Press the reset button for more than 3 seconds. Release the reset button when
the yellow LED flashes.
The burner controller will send out a sequence of pulses, one second on and one
second off. There is a 3-second interval between each sequence. The number of
pulses identifies the probable cause of a problem. See the chart below.
After the determining the cause of the malfunction, correct the issue.
Resetting the burner controller
To return the burner controller to the operation mode, reset the burner controller by
pressing and holding the reset button for 1–3 seconds. The burner will restart after
a 2-second pause.
Press reset
for
>
3s
3s
Pulses
Pulses
RED LED on
wait at least
10s
Interval
Lock-out
wc_gr008353
Signal
Probable Cause
2 pulses
The flame does not stabilze at the end of the safety time due to one of the
following:
– faulty ionization probe
– faulty or soiled gas valves
– neutral/phase exchange
– faulty ignition transformer
– poor burner regulation (insufficient gas)
3 pulses
Minimum air pressure switch does not close due to one of the following:
– make sure pressure switch trips to produce lockout
– air pressure switch faulty
– air pressure switch incorrectly regulated
– fan motor does not run
– maximum air pressure switch operating
4 pulses
Minimum air pressure switch does not open or light in the chamber before
firing due to one of the following:
– air pressure switch faulty
– air pressure switch incorrectly regulated
7 pulses
Loss of flame during operation due to one of the following:
– poor burner regulation (insufficient gas)
– faulty or soiled gas valves
– short circuit between ionization probe and earth
10 pulses
– Wiring error or internal fault
wc_gr008354
Содержание 5000620856
Страница 6: ...ghi_tx001257gb_FM10 fm 6 Foreword HI750 ...
Страница 27: ...HI750 Labels ghi_si000380gb_FM10 fm 27 BB CC FF ...
Страница 115: ...wc_tx003699gb_FM10 fm 115 Kubota Genset Genset Maintenance ...
Страница 122: ...ghi_td000360gb_FM10 fm 122 Technical Data HI750 Notes ...
Страница 135: ...HI750 Schematics ghi_tx001261gb_FM10 fm 135 13 Schematics This page is intentionally left blank ...
Страница 142: ......
Страница 143: ......