UNIFREM v.3.41x
10 May 2017
Page 49 from 180
Name [ID]
Description
Def.
Control panel [1504]
Command macro for command over the UNIPANEL control panel.
Binary + preset freq.
[1505]
Command macro for command over the binary inputs with discrete preset
frequency setpoint values.
AIN freq. [1506]
Command macro for command over the binary inputs with setpoint frequency
over the analog input..
MODBUS [1507]
Command macro for command over MODBUS industrial protocol.
PROFIBUS [1508]
Command macro for command over PROFIBUS industrial protocol.
Up/down
commands
[1509]
Command macro for command over the up (increasy frequency) and down
(decrease frequency) commands.
Pressure
regulation
(bar) [1510]
Command macro for pressure control over the inbuilt process controller
(PID).
7.4.2 START STOP RESET
Group of parameters number [192]
MENU \ SETTINGS \ COMMANDS \ START STOP RESET
Name [ID]
Description
Def.
Start source
[194]
Setting the converter start source. The START command generates the desired voltage
and frequency on the U,V,W outputs (or U,V for a single phase load).
BIN1
Control panel
Pressing the green START button on the control panel causes the converter to start. The start
is canceled by pressing the red STOP button.
Permanent
start
The converter starts immediately after the switch-on.
BIN1
The converter start after the activation of the 1st binary input.
BIN2
The converter starts after the activation of the 2nd binary input.
BIN3
The converter starts after the activation of the 3rd binary input.
BIN1, 2
The converter starts after the activation of the 1st or 2nd binary input.
BIN1, 3
The converter starts after the activation of the 1st or 3rd binary input.
BIN1, 4
The converter starts after the activation of the 1st or 4th binary input.
MODBUS
The converter start is controlled over the serial communication. See the MODBUS serial
communication protocol.
PROFIBUS
The converter start is controlled over the serial communication. See the PROFIBUS serial
communication protocol.
Special
The converter start is controlled by a special preset signal and switching thresholds, see [987]
(page 50).
MODBUS 2
The converter start is controlled over the serial communication. See the MODBUS serial
communication protocol.
Reset source
[704]
Setting the converter reset source. PWM generating will be turned off. It can be used as
an emergency stop. No fault will be generated, only a warning. RESET is needed for
example in applications where the motors are switched at the output. Before switching
the power output, PWM outputs should be blocked, otherwise there is a high risk of
damage to the power elements of the converter.
BIN4
Look choises of parameter's Quick stop source. [986] (page 49)
Quick
stop
source. [986]
Setting the source of the quick stop. It is necessary to cancel and then start the
converter start command again for the converter to start after a quick stop. It is used to
stop the machinery with working personnel, which comes into contact with the rotating
parts. For example, signal light barrier or door limit switch. When active, the drive will
stop by following the faster deceleration ramp, defined by the time parameter Quick
STOP [806] (page 50).
None
None
Function is inactive.
BIN1
Function is activated by activation of the 1st binary input.
BIN2
Function is activated by activation of the 2nd binary input.
BIN3
Function is activated by activation of the 3rd binary input.
BIN4
Function is activated by activation of the 4th binary input.
BIN5
Function is activated by activation of the 5th binary input.
BIN6
Function is activated by activation of the 6th binary input.