UNIFREM v.3.41x
10 May 2017
Page 116 from 180
Name [ID]
Description
Def.
converter or master do not communicate with the Profibus module.
After the defined idle time, warning " W41-Profibus Timeout (page 30)" or fault " E37-
Profibus Timeout (page 33)" is generated.
□ Fault | □ Warning
PB
Fault
timeout [814]
Timeout of communication interruption with Master. After this time, fault E37-Profibus
Timeout (page 33) is generated.
5,00 s
0,10
s
÷
3600,00 s
PB Warning
timeout [815]
MODBUS communication timeout, After communication error longer than this time,
warning " W41-Profibus Timeout (page 30)" is generated. If a Modbus protocol fault
and warning are evaluated at the same time, see PB Idle [813] (page 115), then this
parameter must be lower than the parameter PB Fault timeout [814] (page 116),
otherwise the warning is not generated.
2,00 s
0,10
s
÷
3600,00 s
PB Warning
mode [816]
Defines what action should the converter take after warning " W41-Profibus Timeout
(page 30)" occurs.
Reset
Reset
Converter goes to reset.
Stop
Converter stops.
Quick stop
Converter stops (Quick stop).
No action
Converter will not respond to warnings.
PB
Type
[1486]
Specifies the format of transmission of operational variables.
2
PD
values
2 PD values
It is possible to simultaneously transmit two variables only in the format described by the
documentation.
4 PD values It is possible to transmit 4 values as 16-bit numbers.
VQFREM
It is possible to transmit 4 values as 16-bit numbers, by addresses VQFREM.
PB Options
[1587]
□ Normalized
REF and ACT variables will be normalized to 4000h.
□ Fixed APD
Selection of PD variables, it is set by parameters [1586] (page 116), not by the
communication.
Parameters PROFIBUS
Group of parameters number [1586]
MENU \ SETTINGS \ COMMUNICATION \ PROFIBUS \ PARAMETERS PROFIBUS
Name [ID]
Description
Def.
APD
1
[1578]
[42] Current
MT
Signal
APD
2
[1579]
[66] Power
Signal
APD
3
[1580]
-
Signal
APD
4
[1581]
-
Signal
Dig.
1
[1582]
Determining the last transferred digit from the left.
-
- | - | - | - | - | - | - | - | - | - | - | - | - | - | - | -
Dig.
2
[1583]
The magnitude of 10 that determines the last transferred digit from the left. (..., 1
tens, 0 ones, -1 tenths, ..).
-
Look choises of parameter's Dig. 1 [1582] (page 116)