Name [ID]
Description
Def.
□ Undervoltage
Fault " E5-Undervoltage (page 32)" will not be logged to the fault history.
□
Supply
overload
Fault " E16-Supply overload (page 32)" will not be logged to the fault history.
□ Safety input
Fault " E14-Safety input (page 32)" will not be logged to the fault history.
Par.
changed
[1175]
Allows creating the parameter changes history.
Control panel
■ Control panel
All parameter changes by control panel are recorded.
□ MODBUS
All parameter changes over MODBUS are recorded.
□ PROFIBUS
All parameter changes over PROFIBUS are recorded.
7.8.5 WARNINGS
Group of parameters number [964]
Setting the conditions of generating the individual warnings and their storing to the fault history.
MENU \ SETTINGS \ FAULTS AND WARNINGS \ WARNINGS
Name [ID]
Description
Def.
Warnings [705]
Restricts the displayed warnings to the list of more important warnings.
Basic
Basic
Some warnings, which are not neccesary for basic users, will be suppressed.
Expert
All available warnings and function messages will be displayed.
Cooler
temperature
warning [767]
Temperature, at which the cooler displays a warning " W6-Cooler temperature
(page 28)".
75,0
°C
40,0 °C ÷ 120,0 °C
CB
temperature
warning [204]
Temperature, at which the converter displays a Control board (CB) overheat
warning " W7-CB temperature (page 28)".
55,0
°C
20,0 ÷
Fault
3
3
Refer to chapter 3.2
(str. 14) by product type.
External
warning
source [560]
External warning source settings. If the source is active, the warning " W49-
External warning (page 30)" becomes active. It is used as signalization of any
desired event. It does not influence the converter operation.
None
Look choises of parameter's Quick stop source. [986] (page 49)
Warning log [968]
Selection from warnings 1-32, which will be logged to the fault history at the time
they occur.
Look choises of parameter's Warning [250] (page 24)
Warning
log
2
[969]
Selection from warnings 33-64, which will be logged to the fault history at the
time they occur.
Look choises of parameter's Warning2 [424] (page 24)
SPECIAL SETTING
Group of parameters number [563]
Setting the special source of external warning
MENU \ SETTINGS \ FAULTS AND WARNINGS \ WARNINGS \ SPECIAL SETTING
Name [ID]
Description
Def.
Ext. warning
signal [965]
Signal that is evaluated if the warning " W49-External warning (page 30)" occurs
or not. It is used as an external event warning. Warning does not block the
converter operation. Either numeric or discrete signal can be chosen.
[184]
Binary
inputs
Signal
Ext. warning
[966]
Conditions for external warning.
Look choises of parameter's Binary inputs [184] (page 17)
Ext. warning
inactive [967]
External warning is deactivated: In case of a numeric signal if the signal value is
lower than the defined level.
Look choises of parameter's Binary inputs [184] (page 17)