Current MT signal selection (diagnostic value) for the second input of LB1:
Parameter ID: 580
MENU
–
> SETTINGS
–
> FUNCTIONS
–
> LOGICAL BLOCKS
–
> LB1 (Fast)
–
> LB1_2 Signal=
Current MT
Logical value of the LB1 second input is 1 if the signal value
Current MT > 1[A]
:
Parameter ID: 581
MENU
–
> SETTINGS
–
> FUNCTIONS
–
> LOGICAL BLOCKS
–
> LB1 (Fast)
–
> LB1_2 switch on
= 1 A
Logical value of the LB1 second input is 0 if the signal value
Current MT < 1[A]:
Parameter ID: 582
MENU
–
> SETTINGS
–
> FUNCTIONS
–
> LOGICAL BLOCKS
–
> LB1 (Fast)
–
> LB1_2 switch off
= 1 A
Second input signal of LB1 is necessary to negate to fulfill the entry condition
Current MT < 1[A], because the function of logical block comparative operator is “ > “.
Parameter ID: 1008
MENU
–
> SETTINGS
–
> FUNCTIONS
–
> LOGICAL BLOCKS
–
> LB1 (Fast)
–
> LB1 Level = Input
2 negated
Logical block LB2 selection and setting:
Parameter ID: 168
MENU
–
> SETTINGS
–
> FUNCTIONS
–
> LOGICAL BLOCKS
–
> LB2 (Fast)
LB2 first input has the logical value 1 at logical value 1 of the LB1 output. Operation logical product
- AND is selected for LB2 and LB2 output signal is brought to the second negated input of LB2.
LB2 output switching on and off according to the set time of switch on and switch off of the LB2
logical block is achieved.
Parameter ID: 626
MENU
–
> SETTINGS
–
> FUNCTIONS
–
> LOGICAL BLOCKS
–
> LB2 (Fast)
–
> LB2 Operation =
AND
Parameter ID: 1009
MENU
–
> SETTINGS
–
> FUNCTIONS
–
> LOGICAL BLOCKS
–
> LB2 (Fast)
–
> LB2 Level = Input
2 negated.
Signal selection for the first LB2 input:
Parameter ID: 583
MENU
–
> SETTINGS
–
> FUNCTIONS
–
> LOGICAL BLOCKS
–
> LB2 (Fast)
–
> LB2_1 Signal =
Logical blocks
Signal of first input of LB2 has the logical value 1 if the output signal of LB1 has the logical value 1:
Parameter ID: 584
MENU
–
> SETTINGS
–
> FUNCTIONS
–
> LOGICAL BLOCKS
–
> LB2 (Fast)
–
> LB2_1 switch on
= LB1
The output signal of LB2 is signal for the second negated LB2 input. We want to achieve switching
on and off of the LB2 output (alternation of discrete states (0.1) with the logical block according to
the set time of switch on and off of the logical block off LB2.
Parameter ID: 586
MENU
–
> SETTINGS
–
> FUNCTIONS
–
> LOGICAL BLOCKS
–
> LB2 (Fast)
–
> LB2_2 Signal =
Logical blocks