47/60 NT00000658-TEDH-V-F400-ECOWATT-AN-210609
Refer to the corresponding paragraph below for the connection and configuration of your unit.
Default configuration settings
A USB to RS 485 converter is required to connect to the registers via a PC, as well as an interface of the
same type as ModBus Doctor.
Three-phases units*
MODBUS address
80
Baut rate
19200
START Bit
1
STOP Bit
1
Parity
NONE
* For extra information please refer to the controller O&M (contact the After-Sales service department).
Table input
The "Inputs" table allows you to read the following information:
Register
Fault
Value
Description
0
Power on
0-1
1 = Voltage too low to operate
1
Over voltage
0-1
1 = Voltage too high to operate
2
SW over current
0-1
1 = current protection of the IGBT software
3
On temperature
0-1
1 = Converter too hot to operate
4
Phase loss
0-1
1 = Loss of phase or of main supply
5
Earth current fault
0-1
1 = asymmetrical load (sum of all currents >3 A)
6
CRC settings
0-1
1 = Monitoring of parameters has failed (TBD)
7
Driver fault
0-1
1 = Transistor driver initialization fault
8
ADC fault
0-1
1 = ADC conversion error
9
SPI communication fault
0-1
1 = No communication between the processors
10
Reduction in power
0-1
1 = Reduction in the power of the controller.
11
Stoppage of the reduction in
power
0-1
1 = Stop (motor stop) temperature of the controller reached
12
HW over current
0-1
1 = IGBT software current protection
13
FLW enabled
0-1
1 = Weakening of the active field
14
System error
0-1
1= Machine error
Input register table
The "Input Register" table allows you to read the following information:
Register
Function
Resolution
Description
Three-phases units
0
Speed
1
tr/min
2
Power
1
W
9
Input An1
0,01
V
10
Input An2
0,01
V
The communication protocol and the Modbus exchange table are available on our website www.vim.fr
NT00000673-KUBAIR-TED-REGULATION.
For all other information on the setting of Modbus, contact the After-Sales service department.