35/60 NT00000658-TEDH-V-F400-ECOWATT-AN-210609
Modbus connection between each TEDH/V ECOWATT
®
and the touchscreen remot control ETDZ R
To connect each TEDH/V ECOWATT
®
to each other and to the remote control, use Modbus flat cable /
telecommunication cable, 6 conductors, 30AWG/0.066mm², with RJ12 connectors at each end.
U V W PE
BR- BR+
A
B
Gnd
+10V
0-10V
GND
D2
D1
D0
Gnd
R2 No
R2 C
R2 Nc
R1 No
R1 C
R1 Nc
Gnd
+24V
+10V
AO_1
DI_4
DI_3
AI_2
Therm
Gnd
A
B
C
U V W PE
BR- BR+
A
B
Gnd
+10V
0-10V
GND
D2
D1
D0
Gnd
R2 No
R2 C
R2 Nc
R1 No
R1 C
R1 Nc
Gnd
+24V
+10V
AO_1
DI_4
DI_3
AI_2
Therm
Gnd
A
B
C
U V W PE
BR- BR+
A
B
Gnd
+10V
0-10V
GND
D2
D1
D0
Gnd
R2 No
R2 C
R2 Nc
R1 No
R1 C
R1 Nc
Gnd
+24V
+10V
AO_1
DI_4
DI_3
AI_2
Therm
Gnd
A
B
C
The RJ12 connector is on the back of the remote control.
A rectangular notch in the blue cover of the controller allows the passage of flat cables.
Touch screen
ETDZ R
TEDH/V F400 ECOWATT® 01
TEDH/V F400 ECOWATT® 02
TEDH/V F400 ECOWATT® 03
System configuration
Power all the TEDH/V ECOWATT
®
units in your system, then configure your system on the ETDZ R by
following the instructions below :
LANGUAGE
DEVICE SCAN
CONNECTION
English
2/2 DEVICES CONNECTED
CONNECT X DEVICES
Deutsch
DV 1
SCANNING...
DV 1
DV 2
DV 2
Select English and then press the
right arrow key
Wait until all TEDH/V F400
ECOWATT
®
connected to the system
appears under scanning, then press
CONNECT X DEVICES
All TEDH/V F400 ECOWATT
®
units
must have a green V on the front,
which means that they are connected
to the system. Press the right arrow
DVX represents a TEDH/V F400 ECOWATT
®
. X is the number of the Modbus address.