26/60 NT00000658-TEDH-V-F400-ECOWATT-AN-210609
Continued table
Register Address
Function
Common for EC (PM) & FC (AC) configuration
Range / Value
Resolution / Option
Unit
4x0017
16
Modbus ID
1 - 247
1
-
4x0018
17
ModbusResponseDelay
0 - 200
1
ms
4x0020
19
Number of retries
-1 - 100
1
-
4x0022
21
CommTimeout
0 - 240
1
Sec.
4x0023
22
CommRate
0
9600
bps
1
19200
bps
2
38400
bps
3
115200
bps
4
57600
bps
4x0024
23
Parity
0
None
-
1
Odd
-
2
Even
-
4x0025
24
Stop Bits
0
INVALID
-
1
1
-
2
2
-
4x0026
25
DigIn1 config
0
Disabled
-
1
Start/stop
-
2
AlarmReset
-
3
MB_IDs_2
-
4
Invert 0-10V (open =
inverted)
-
5
Rotation
-
6
Firemode
-
7
Motor Overheat
-
8
Invert 0-10V
(open = not inverted)
-
9
Motor output off
-
10
Modbus Disable
-
11
FiremodeMax
-
12
Digital Dual Speed
-
4x0027
26
DigIn2 config
0
Disabled
-
1
Start/stop
-
2
AlarmReset
-
3
MB_IDs_2
-
4
Invert 0-10V (open =
inverted)
-
5
Rotation
-
6
Firemode
-
7
Motor Overheat
-
8
Invert 0-10V
(open = not inverted)
-
9
Motor output off
-
10
Modbus Disable
-
11
FiremodeMax
-
12
Digital Dual Speed
-
4x0028
27
DigOut config
0
Disabled
-
1
TachoOut
-
2
RunningStart
-
3
AlarmOut
-
4
RunningSpin
-
5
Set output status via coil
stat 24
-
6
Single Error Alarm
-
4x0029
28
MotorConfigVar
0 - 65534
1
-
4x0030
29
FanConfigVar
0 - 65534
1
-