20/60 NT00000658-TEDH-V-F400-ECOWATT-AN-210609
5.1.2 Alarms and operating status indication
LED indication
An LED is present next to cable glands on the controller.
Constant green LED: the supply voltage is connected.
Green LED flashing: Modbus communication is active.
Constant red LED: at least one critical alarm is active.
Flashing red LED: a non-critical alarm is active.
Consultation of alarms and operating status of the extractor by the remote controller ETDZ A
(optional)
The ETDZ A remote control is connected to the Modbus RJ12 "C" connector on the terminal block.
The ETDZ A remote control (touch control) provides accurate information on the type of alarm.
You can view an alarm via ETDZ A, following the instructions below:
Warning & alarms
Setpoint 0%
RESET
ALARM/WARNING DESCRIPTION
Current speed
Drive type
Drive power in
Controle type
_ _ _ RPM
PM
_ _ _ kW
0-110V
Alarm 1001
Motor stop due to alarm
Alarm 1202
One or more lacking phases in
motor connection (U, V, W)
A bell appears at the top left of the
screen, press it to view the alarms.
Alarm board - requires ETDZ remote control
Alarm code
Trigger
Motor running / action
1101 Input voltage low
Voltage too low to operate
Reduced performance
1102 input voltage high
Voltage too high to operate
Motor stops after 5 restarts caused by
the same fault within 60 min.
2301 Temperature high
The ambient temperature around the
controller is too high
Reduced performance
2101 Input phase warning
Phase loss, unbalanced phases
Motor stops after 5 restarts caused by
the same fault within 60 min.
2203 Brake choper fault
The rotor cannot rotate due to
mechanical locking of the rotor or
impeller
Motor stops after 5 restarts caused by
the same fault within 60 min.
1202 Motor phase error
One or more phases / One or more
motor cables are disconnected
Motor stops after 5 restarts caused by
the same fault within 60 min.
2204 Ext. 24V overload
Overload or short circuit in the supply
v24V
Reduced performance
Reset alarm via terminal block
After the problem has been solved, you can reset an alarm by closing the contact between DI2 (terminal
7) and GND (terminal 6), an impulse is sufficient (Terminals see "5.1.1 Controller terminal block", page
19).