19/60 NT00000658-TEDH-V-F400-ECOWATT-AN-210609
5. COMMISSIONING AND CONFIGURATION OF ONE-PHASE CONTROLLERS
SIZES 355/400/450
5.1 Presentation of the VENTIDRIVE single-phase controller
The ECM motor controller controls the motor according to an adjustment potentiometer on the controller,
an external 0-10V signal or a setpoint given by GTC ModBus.
5.1.1 Controller terminal block
U V W PE
BR- BR+
A
B
Gnd
+10V
0-10V
GND
D2
D1
D0
Gnd
R2 No
R2 C
R2 Nc
R1 No
R1 C
R1 Nc
Gnd
+24V
+10V
AO_1
DI_4
DI_3
AI_2
Therm
Gnd
A
B
C
L N PE
Factory-fitted motor terminal block
It is imperative that the U-V-W cable
sequence is observed
Factory-fitted terminal block
One-phase
KUBAIR 355
KUBAIR 400
KUBAIR 450
Running status LED
RJ 12 - Modbus connectors
Command terminal block.
The various control functions are defined
in the operating instructions.
A
B
Gnd
+10V
0-10V
GND
D2
D1
D0
Gnd
R1 C
R1 Nc
Gnd
+24V
+10V
AO_1
DI_4
DI_3
AI_2
Therm
Gnd
R2 No
R2 C
R2 Nc
R1 No
Command terminal block
Modbus
Speed control via analogue input 0-10V
VAV versions : factory wired potentiometer
COP and CAV versions: VCHV-A factory wired
Digital input Reset alarm
Digital On/Off input (Shunt wired from factory)
Not used
24V
10V
Total consumption
max 450mA
0-10V outlet, representative of the motor speed
Digital input disabled
Digital input Fire mode (Thermocontact wired from factory)
1
2
3
4
5
6
7
8
9
10
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
No function
Output 1 relay
Running relay
Output 2 relay
Fault relay
Max 1A at
30VDC and 24VAC
Terminal block accessible
under the blue cover
by means of 6 TX20 screws
Motor connection - Factory-made
Control connection
PE M25 Multipass - 3 passes :
- 2 available in VAV version without display
- 1 available on all other versions
Cable sheath Ø 6.8 to 9 mm
Power connection - Factory-made to INTZ
TED 355
TED 400
TED 450