Only one detector can be supported in alarm per zone.

*UL and ULC Listed 

If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted.   

 

 

 

Sync Modules: 

Amseco - SMD10-3A 

Gentex - AVSM 

     System Sensor - MDL            Wheelock - DSM 12/24

Fenwal (Max. No. Of Detectors Per Zone Is 25)

Det. Model   

Identifier   

Base Model   

Identifier

CPD-7051*                                                              I51FE1 

2-WIRE 

 

FE51A

PSD-7155*                                                              P55FE1 

2WRLT 

 

FE52A

PSD-7156*                                                              P56FE1 

2WRB 

 

FE55A

All of the above Fenwal detectors and bases can be used in any combination

Retrofit Base Adaptor 70-501000-003, Identifier MAFE1 (for series 70-201000 Bases, Models -001, -002, -003 and -005)

Duct Housing with Detector Base DH-51, Identifier DH22FE5 (for CPD-7051 and PSD-7155 detectors only)   

 

 

 

Potter (Max. No. Of Detectors Per Zone Is 25)

Det. Model   

Identifier   

Base Model  

Identifier

PS-24* 

HD-3(HOCHIKI) 

SB-46 

HB-71(HOCHIKI)

   

 

 

 

 

HB-54(HOCHIKI)

  

   

SB-93 

HB-3  (HOCHIKI

PS-24H 

HD-3(HOCHIKI) 

SB-46 

HB-71(HOCHIKI)

   

 

 

 

 

HB-54(HOCHIKI)

Potter (Max. No. Of Detectors Per Zone Is 30)

Det. Model   

Identifier   

Base Model  

Identifier

CPS-24 

HD-3(HOCHIKI) 

SB-46 

HB-54(HOCHIKI)

CPS-24N 

HD-3(HOCHIKI) 

SB-46 

HB-54(HOCHIKI)

Содержание VFR400

Страница 1: ...Manual 5403548 Rev W 8 17 VFR 400 Releasing Control Panel Installation Operation and Instruction Manual Releasing Panel for Sprinkler and Clean Agent Systems All specifications subject to revision ...

Страница 2: ...Module 11 RA 4410RC Remote Annunciator 11 RCDS 1 Release Circuit Disconnect Switch 11 Basic Operation 11 Initiating Device Circuits Alarm Condition 12 Alarm 12 Low Air Alarm 12 Supervisory 12 Trouble Conditions 13 Notification Appliance Releasing Circuits 13 Loss Or Reduction Of AC Power 13 Notification Appliance Releasing Circuits 13 Low Battery Voltage 14 Loss of Auxiliary Power Output 14 To Sil...

Страница 3: ...nable Disable 26 One Man Walktest 26 VFR 400 Standard Program Information Wiring Diagrams 27 78 VFR 400 Custom Program Information Water Based Extinguishing 79 82 VFR 400 Custom Program Information Water Based Extinguishing 83 88 2 Wire Smoke Detector And Synchronization Module Compatibility Data 89 4 WIRE HEAT DETECTOR COMPATIBILITY IDENTIFIER A 91 Viking Firecycle normally closed heat detectors ...

Страница 4: ... an AC power failure The batteries and release panel shall be tested and maintained in accordance with the testing and maintenance requirements of NFPA72 In order for emergency forces Fire departments etc to respond to events associated with this panel the panel must transmit trouble supervisory and alarm signals to a monitoring facility either directly or through a main building fire panel A prob...

Страница 5: ...only Supervisory Zones Supervisory Tamper Low Air Supervisory High Air Low Air Alarm NOTE Only zones programmed as Detection Waterflow Linear Heat Manual Release Firecycle and Low Air Alarm can be mapped to outputs programed as release NOTICE TO USERS INSTALLERS AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES This product incorporates field programmable software In order for the product...

Страница 6: ...ted per NEC 760 and UL 864 Section 14 4 Initiating Circuit Disable feature Output Disable feature One Man Walktest feature with automatic 30 minute restoration and releasing circuit disable Class B Abort circuit available in Chemical mode Three Abort modes available Pre Discharge timer from 0 60 seconds available in Chemical mode only Manual Release 0 30 seconds predischarge timer in Chemical Mode...

Страница 7: ...rea is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference Remote annunciator output Resettable 4 wire smoke detector power Options Refer to Appendix A of the manual for product data sheets 1 CAM Module to convert one Class B Indicating Appliance Circuit to one Class A circuit 2 CA2Z Module to...

Страница 8: ...h Supervisory 1 Abort Supervisory 2 Power Trouble Supervisory Abort Trouble System Trouble Earth Fault Signal Silenced CONDITION STATUS LED State Trouble Non Silenced Flashing Trouble Silenced Steady ON Alarm Non Silenced Flashing Alarm Silenced Steady ON Supervisory Non Silenced Flashing Supervisory Silenced Steady ON Pre discharge Flashing Discharging Steady ON Control Buttons Signal Silence Mom...

Страница 9: ...pliances are required for evacuation selectable tone appliances shall be used The notification outputs do not provide synchronization The notification appliances shall be compatible with the sync module selected The sync module shall be installed as per manufacturers instructions Synchronization is limited to only one circuit and not between circuits Systems intended for the release of Halon 1301 ...

Страница 10: ...must be programmed for cross zoning for the IRI mode to function Mode 3 NYC This mode is not UL listed Activation of the abort circuit during the pre discharge countdown adds 90 seconds to the original pre discharge time This is a one time feature Repeated pressing of the abort button has no effect The pre discharge timer resumes when the abort button is released Mode 4 30 Second Abort This mode i...

Страница 11: ...10RC remote annunciator Maximum 2000 with 22 AWG 4000 with 20 AWG shielded cable Optional Accessories see technical data sheets in Annex A at the back of this manual CA2Z Module Class A Initiating Device Circuit Converts two Class B initiating device circuits to two Class A circuits Not to be used for 4 wire smoke detectors unless approved by local AHJ ARM 44 Auxiliary Relay Module To provide 8 in...

Страница 12: ...ribed as SUPERVISORY TAMPER LOW AIR SUPERVISORY or HIGH AIR 6 Activation of yellow OUTPUT indicator s on LED display for the Notification appliance circuit s described as SUPERVISORY BELL 7 Activation of the amber SUPERVISORY LED in a flashing modes well as the corresponding zone LED NOTE The SUPERVISORY LED will continue to flash until all events in the SUPERVISORY queue are viewed This is accomp...

Страница 13: ...E The TROUBLE LED will continue to flash until all events in the TROUBLE queue are viewed This is accomplished by scrolling through all of the events by use of the scroll up and scroll down buttons The LED will go steady after all trouble events have been viewed 5 Activation of red ALARM indicator on LED display 6 Activation of red OUTPUT indicator s on LED display module for the output circuit s ...

Страница 14: ...tigating and determining that an emergency condition does not exist Low Battery Voltage Loss of or reduction of battery voltage to 22 volts will result in the following 1 Activation of trouble relay contacts trouble LED and local buzzer 2 Operation of any output circuits that have been described as TROUBLE BELL 3 TROUBLE and BATTERY displayed on LCD 4 Activation of yellow POWER TROUBLE indicator o...

Страница 15: ...IGNAL SILENCE LED will light Any zone programmed as WATERFLOW is considered non silenceable so the SIGNAL and TBL SUP ACKNOWLEDGE buttons will have no effect on the flashing zone and output LED s A buzzer on the annunciator sounds for any trouble condition When the panel is in a normal state pressing the LAMP TEST button can be used to test the LED s The release panel supervises and communicates w...

Страница 16: ...tely 1 2 in order to clear the cross beam of the cabinet on which the module rests Remove the module and set aside 3 Install all required conduits external wiring and devices and make all connections that are external to the panel Replace the module With the AC power still turned off at the circuit breaker panel connect the AC hot neutral and ground wires to the terminal block TB201 as shown on th...

Страница 17: ...ll in the name address and telephone number of the servicing agency on the appropriate instruction sheet Frame and place this sheet adjacent to control panel at eye level BATTERY SIZE CALCULATIONS To use Calculation Table 1 List in column 1 all devices used in the system include all modules bells horns door holders and smoke detectors see table 1 or manufacturers specifications 2 List in column 2 ...

Страница 18: ...Y TROUBLE SILENCED FIRE DRILL ACK NOWLEDGE SIGNAL SILENCE RESET 9 RELAY TERMINALS ROTARY SWITCH ROTARY SWITCH ARM 44 SET TO MODE 2 VFR 400 RS 485 CONNECTION COM NO NC COM NO NC S S 24VDC RS 485 COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC ZONE1 ZONE1 SUP ZONE 2 ZONE2 TBL ZONE3 ZONE3 ALM ZONE4 ZONE4 ALM OUT1 SUP OUT1 OUT2 TBL OUT2 OUT3 ALM OUT3 OUT4 ALM OUT4 DISABLE LATCH MODE 2 MODE...

Страница 19: ...l Standby Current Alarm mA Per Unit Total Alarm Current TABLE 1 CURRENT REQUIREMENTS Add 23 mA plus current requirement of all devices connected for each output programmed as Trouble Bell Includes one zone short circuit current Use a battery with a higher AH rating than Required AH Total mA Convert to A Total A 5 min 12 or 10 min 6 Total Alarm AH Total Standby AH Total AH Efficiency Factor Require...

Страница 20: ...ors are connected and a The electric light power Class 1 and nonpower limited fire alarm circuit conductors are routed to maintain a minimum of 0 25 in 6 35mm separation from the conductors and cables of power limited fire alarm circuits or b The circuit conductors operate at 150 volts or less to ground and also comply with one of the following 1 The fire alarm power limited circuits are installed...

Страница 21: ...tter model PS 24 and CPS 24 Photoelectric Detectors Typical Class B Wiring Using SB 46 Base Typical Class A Wiring NOTE The 6 diameter bases will mount on a 3 or 4 octagon box or a 4 square box Typical 4 Wire Wiring EOL 5 1k FROM CONTROL PANEL ZONE TERMINALS RESETTABLE AUX POWER DWG 3521 5VKG PAM 4 End of Line Wiring ...

Страница 22: ...22 VFR 400 5403548 REV W 8 17 ACTIVE ALARM CONDITION SPECIAL APPLICATION VFR 400 Connection Drawing For additional information see text in this manual Identifier A ...

Страница 23: ... then move the PROGRAM switch up The panel will respond with ONE MAN WALKTEST and the time The trouble LED will light Any output described as RELEASING will automatically be disabled After 30 minutes of no activity in the walk test mode the panel automatically reverts to normal operation 6 Operate each initiating device on all zones All audible and visual alarm devices should operate for about 3 s...

Страница 24: ... the Programming Mode buttons The SET button sets the message on the display into the memory The SELECT button scrolls through the selections available for the function displayed The FUNCTION button allows the user to skip the function without changing the program To program push the Program Switch down There is no capability to back up screens in the program mode If a mistake was made during prog...

Страница 25: ...ill increase the minutes FUNCTION Whenfinshedsettingtheminutes PresstheFUNCTIONbutton Theminuteswillchangeto hours Continue this process and change the DAY MONTH and YEAR When you have finished changing the year press the FUNCTION button A display similar to the following will appear Password This display prevents unauthorized programming of the panel by requiring the user to enter the proper pass...

Страница 26: ... A M 1 After 30 minutes of no activity the panel automatically reverts to normal Output Enable Disable This display allows the user to ENABLE or DISABLE any of the output circuits NFPA 72 prohibits the use of a software disconnect for RELEASE CIRCUITS A physical means of disconnecting a RELEASE CIRCUIT shall be used such as the Potter RCDS 1 SET After selecting ENABLED or DISABLED press the SET bu...

Страница 27: ...s continuous The soak timer is user selectable to 30 60 or 90 seconds or 2 20 minutes in 1 minute increments VFR 400 STANDARD PROGRAM INFORMATION The VFR 400 has 16 standard programs which are detailed in the following pages Selecting one of these programs will automatically program every function of the panel except the custom banner and zone message functions NOTES The release discharge time is ...

Страница 28: ...peration Activation of Conventional Detection zone 1 or 2 or Manual Release zone 4 will activate output 3 Release Solenoid and output 1 General Alarm Activation of Waterflow zone 3 will activate output 2 Waterflow and output 1 General Alarm Activation of Low Air Supervisory zone 1 or Valve Tamper Supervisory zone 2 will operate output 4 Supervisory Bell NOTES 1 Connect EOL Diode assembly IN SERIES...

Страница 29: ... RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS EARTH SUP ABORT TBL TBL SUP ACKNOWLEDGE TBL SUP ACKNOWLEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR on all unused circu...

Страница 30: ...ivation of Conventional Detection zone 1 will activate output 2 Release Solenoid 1 and output 1 General Alarm Activation of Conventional Detection zone 2 will activate output 3 Release Solenoid 2 and output 1 General Alarm Activation of Waterflow zone 3 or 4 will activate output 1 General Alarm and output 4 Waterflow Activation of Valve Tamper Supervisory zone 1 or Low Air Supervisory zone 2 will ...

Страница 31: ...EASING SERVICE SIGNAL SILENCE HOLD FOR 2 SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOWLEDGE TBL SUP ACKNOWLEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Le...

Страница 32: ... of Conventional Detection zone 1 will activate output 1 General Alarm Activation of Low Air Alarm zone 2 will activate output 4 Supervisory Bell Activation of Waterflow zone 3 will activate output 2 Waterflow and output 1 General Alarm Activation of Manual Release zone 4 will activate output 3 Release Solenoid and output 1 General Alarm Activation of Low Air Supervisory zone 1 or Valve Tamper Sup...

Страница 33: ...OLD FOR 2 SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOWLEDGE TBL SUP ACKNOWLEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR on a...

Страница 34: ... Preaction System with Electric Release 2 Deluge System with Electric Release 3 Non Interlocked Preaction System with Electric Release 4 Double Interlocked Preaction System with Electric Pneumatic Release OUTPUTS Indicating Circuits ZONES Initiating Circuits SUP 1 SUP 2 1 2 3 4 Valve Tamper Supervisory Zone for Systems 1 2 Low Air Supervisory Zone for Systems 1 2 Conventional Detection Zone for Sy...

Страница 35: ...NG SERVICE SIGNAL SILENCE HOLD FOR 2 SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOWLEDGE TBL SUP ACKNOWLEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave ...

Страница 36: ...e System with Electric Release 3 Non Interlocked Preaction with Electric Release 4 Double Interlocked Preaction System with Electric Pneumatic Release OUTPUTS Indicating Circuits ZONES Initiating Circuits SUP 1 SUP 2 1 2 3 4 Valve Tamper Supervisory Zone Low Air Supervisory Zone Conventional Detection Zone Low Air Alarm Zone Waterflow Zone Manual Release Zone 1 General Alarm X X X 2 Supervisory Be...

Страница 37: ...ILENCE HOLD FOR 2 SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOWLEDGE TBL SUP ACKNOWLEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed E...

Страница 38: ...ge 5 PROGRAM 6 For One Sprinkler System Viking Sprinkler System Types Release Zone and Manual Release Zone 1 FIRECYCLE III Single Interlocked Preaction Multicycle System 2 FIRECYCLE III Single Interlocked Preaction Multicycle System NYC Special OUTPUTS Indicating Circuits ZONES Initiating Circuits SUP 1 SUP 2 1 2 3 4 Low Air Supervisory Zone Valve Tamper Supervisory Zone FIRECYCLE Detector Zone Lo...

Страница 39: ...HOLD FOR 2 SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOWLEDGE TBL SUP ACKNOWLEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR on ...

Страница 40: ...al Release zone 4 will activate output 1 General Alarm and output 3 Release Solenoid Deactivation of FIRECYCLE Detector zone 1 will start soak timer when timer cycle is complete the output 3 Release Solenoid is deactivated Activation of Low Air Supervisory zone 1 or Valve Tamper Supervisory zone 2 will activate output 2 Supervisory Bell NOTES 1 Connect EOL Diode assembly IN SERIES as shown with So...

Страница 41: ...OLD FOR 2 SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOWLEDGE TBL SUP ACKNOWLEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR on a...

Страница 42: ... is complete the output 3 Release Solenoid is deactivated Activation of Supervisory zone 1 or Valve Tamper Supervisory Zone 2 will activate output 2 Supervisory Bell NOTES 1 Connect EOL Diode assembly IN SERIES as shown with Solenoid on output 3 Release Solenoid and output 4 N O Solenoid Black wire to negative terminal on panel and Red wire through Solenoid to positive terminal on panel 2 Polarity...

Страница 43: ...SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOLWEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR on all unused circuits 2 Connect o...

Страница 44: ...is complete the output 3 Release Solenoid is deactivated Activation of Supervisory zone 1 or Valve Tamper Supervisory zone 2 will activate output 2 Supervisory Bell NOTES 1 Connect EOL Diode assembly IN SERIES as shown with Solenoid on output 3 Release Solenoid and output 4 N O Solenoid Black wire to negative terminal on panel and Red wire through Solenoid to positive terminal on panel 2 Polarity ...

Страница 45: ...ENCE HOLD FOR 2 SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOLWEDGE TBL SUP ACKNOLWEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOL...

Страница 46: ...rlocked Preaction System 2 SUREFIRE Single Interlocked Preaction System NYC Special 3 SUREFIRE Single Interlocked Preprimed Preaction System 4 SUREFIRE Single Interlocked Preprimed Preaction System NYC Special OUTPUTS Indicating Circuits ZONES Initiating Circuits SUP 1 SUP 2 1 2 3 4 Valve Tamper Supervisory Zone Low Air Supervisory Zone Conventional Detection Zone Low Air Alarm Zone Waterflow Zone...

Страница 47: ... HOLD FOR 2 SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOLWEDGE TBL SUP ACKNOLWEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR on...

Страница 48: ...l 3 SUREFIRE Double Interlocked Preprimed Preaction System 4 SUREFIRE Double Interlocked Preprimed Preaction System NYC Special OUTPUTS Indicating Circuits ZONES Initiating Circuits SUP 1 SUP 2 1 2 3 4 Valve Tamper Supervisory Zone Low Air Supervisory Zone Conventional Detection Zone Low Air Alarm Zone Waterflow Zone Manual Release Zone 1 General Alarm X X X 2 Supervisory Bell X X X 3 Release Sole...

Страница 49: ...SIGNAL SILENCE HOLD FOR 2 SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOLWEDGE TBL SUP ACKNOLWEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory ins...

Страница 50: ...lectric Release 4 Double Interlocked Preaction System with Electric Pneu Lectric Release OUTPUTS Indicating Circuits ZONES Initiating Circuits SUP 1 SUP 2 1 2 3 4 Valve Tamper Supervisory Zone Low Air Supervisory Zone Conventional Detection Zone Conventional Detection Zone Waterflow Zone Manual Release Zone 1 General Alarm X X X X 2 Waterflow X 3 Release Solenoid X X X X X 4 Supervisory Bell X X O...

Страница 51: ...OR 2 SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOLWEDGE TBL SUP ACKNOLWEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR on all un...

Страница 52: ... 3 will activate outputs 3 and 4 release solenoids and output 1 General Alarm Activation of Waterflow zone 2 will activate output 1 General Alarm Activation of Valve Tamper supervisory zone 1 or Low air supervisory zone 2 will activate output 2 Low Air Tamper NOTES 1 Connect EOL Diode assembly IN SERIES as shown with solenoids on outputs 3 and 4 Black wire to negative terminal on panel Red wire th...

Страница 53: ...ICE SIGNAL SILENCE HOLD FOR 2 SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOLWEDGE TBL SUP ACKNOLWEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory...

Страница 54: ...ase zone 4 will activate outputs 3 and 4 release solenoids and output 1 General Alarm Activation of Waterflow zone 3 will activate output 1 General Alarm Activation of Valve Tamper supervisory zone 1 or Low air supervisory zone 2 will activate output 2 Low Air Tamper NOTES 1 Connect EOL Diode assembly IN SERIES as shown with solenoids on outputs 3 and 4 Black wire to negative terminal on panel Red...

Страница 55: ...NCE HOLD FOR 2 SECONDS SET RUN PROGRAM FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS SUP ABORT TBL TBL SUP ACKNOLWEDGE TBL SUP ACKNOLWEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR...

Страница 56: ...eral Alarm Activation of Valve Tamper supervisory zone 1 Low air supervisory zone 2 or Low Air alarm zone 2 will activate output 2 Low Air Tamper A trouble condition will prevent output 4 N O from activating NOTES 1 Connect EOL Diode assembly IN SERIES as shown with solenoids on outputs 3 and 4 Black wire to negative terminal on panel Red wire through solenoid to positive terminal on panel Output ...

Страница 57: ...SUP ACKNOLWEDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR on all unused circuits 2 Connect one circuit at a time and apply AC power 3 Connect batteries to the panel 4 Once last connect...

Страница 58: ... is complete output 3 release solenoids is deactivated Activation of Valve Tamper supervisory zone 1 Low air supervisory zone 2 or Low air alarm 2 will operate output 2 Low air Tamper NOTES 1 Connect EOL Diode assembly IN SERIES as shown with solenoids on outputs 3 and 4 Black wire to negative terminal on panel Red wire through solenoid to positive terminal on panel Output 3 has 2 solenoids These ...

Страница 59: ...Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR on all unused circuits 2 Connect one circuit at a time and apply AC power 3 Connect batteries to the panel 4 Once last connection is made move P...

Страница 60: ...of Conventional Detection zone 1 will activate output 1 General Alarm Activation of Low Air Alarm zone 2 will activate output 4 Supervisory Bell Activation of Waterflow zone 3 will activate output 2 Waterflow Activation of Manual Release zone 4 will activate output 3 Release Solenoid and output 1 General Alarm Activation of Low Air Supervisory zone 1 or Valve Tamper Supervisory zone 2 will operate...

Страница 61: ...EDGE 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR on all unused circuits 2 Connect one circuit at a time and apply AC power 3 Connect batteries to the panel 4 Once last connection is made...

Страница 62: ...ctivation of Conventional Detection zone 1 or 2 or Manual Release zone 4 will activate output 3 Release Solenoid and output 1 General Alarm Activation of Waterflow zone 3 will activate output 2 Waterflow and output 1 General Alarm Activation of Low Air Supervisory zone 1 or Valve Tamper Supervisory zone 2 will operate output 4 Supervisory Bell NOTES 1 Connect EOL Diode assembly IN SERIES as shown ...

Страница 63: ...1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR on all unused circuits 2 Connect one circuit at a time and apply AC power 3 Connect batteries to the panel 4 Once last connection is made move...

Страница 64: ...Bell Operation Activation of Conventional Detection zone 1 and 2 or Manual Release zone 4 will activate output 3 Release Solenoid and output 1 General Alarm Activation of Waterflow zone 3 will activate output 2 Waterflow Activation of Low Air Supervisory zone 1 or Valve Tamper Supervisory zone 2 will operate output 4 Supervisory Bell NOTES 1 Connect EOL Diode assembly IN SERIES as shown with Solen...

Страница 65: ...ACK RED 1 Run field wiring and ensure connections are proper by metering wires Resistance reading should be 5 1K ohms with end of line resistor EOLR at last device The end of line resistor is located on the mother board Remove as needed Leave factory installed EOLR on all unused circuits 2 Connect one circuit at a time and apply AC power 3 Connect batteries to the panel 4 Once last connection is m...

Страница 66: ...grammed as SECOND ALARM It will provide a steady output upon activation of a second initiating zone programmed as an alarm zone This is when the pre discharge timer would start and would be the pre discharge signal If a temporal signal is required notification appliances such as Potter H 1224 Select A Horn or others that can produce a temporal tone shall be used This allows the use of strobes and ...

Страница 67: ...67 VFR 400 5403548 REV W 8 17 This page intentionally left blank ...

Страница 68: ...upervisory Detection Detection Detection Detection 1 ALARM INDICATING X X 2 RELEASE XX XX 3 ALARM INDICATING X X 4 RELEASE XX XX OPERATION DESCRIPTION Description Dual Hazard 2 detection zones cross zoned to 1 release circuit and 2 other detection zones cross zoned to another release circuit Inputs 1 supervisory zone 4 detection zones 1 abort circuit Outputs 2 general alarm 2 release circuit Opera...

Страница 69: ...ILENCE STEADY DISCHARGE FLASHING PRE DISCHARGE RUN PROGRAM SET SELECT FUNCTION SCROLL DOWN TBL SUP ACKNOWLEDGE SIGNAL SILENCE SYSTEM RESET SCROLL UP TBL SUP ACKNOWLEDGE VIEWING ANGLE RED OUTPUT LED STEADY ABORT N 120 LAMP TEST RELEASING SERVICE SIGNAL SILENCE HOLD FOR 2 SECONDS ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS See page 83 for smoke detector compatibility data See pages 17 19 for battery in...

Страница 70: ...he abort mode displayed 12 The panel is completely programmed except for the custom banner and zone messages Move the program switch back up PROGRAM 21 ZONES SUPERVISORY 2 1 2 3 4 OUTPUTS Supervisory Detection Detection Detection Detection 1 ALARM INDICATING X X 2 RELEASE X X 3 ALARM INDICATING X X 4 RELEASE X X SUP 1 defaults to abort OPERATION DESCRIPTION Description Dual Hazard 2 detection zone...

Страница 71: ...L SILENCE STEADY DISCHARGE FLASHING PRE DISCHARGE RUN PROGRAM SET SELECT FUNCTION SCROLL DOWN TBL SUP ACKNOWLEDGE SIGNAL SILENCE SYSTEM RESET SCROLL UP TBL SUP ACKNOWLEDGE VIEWING ANGLE RED OUTPUT LED STEADY ABORT N 120 LAMP TEST RELEASING SERVICE SIGNAL SILENCE HOLD FOR 2 SECONDS ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS See page 83 for smoke detector compatibility data See pages 17 19 for battery...

Страница 72: ...NES SUPERVISORY 2 1 2 3 4 OUTPUTS Supervisory Detection Detection Manual Release Detection 1 FIRST ALARM X X 2 SECOND ALARM X X X 3 RELEASE XX XX X 4 ALARM INDICATING X SUP 1 defaults to abort XX Cross Zoned OPERATION DESCRIPTION Description Single Hazard 2 detection zones cross zoned to 1 release circuit A manual station zone and a discharge confirmation zone Also first and second alarm notificat...

Страница 73: ...ARM SIGNAL SILENCE STEADY DISCHARGE FLASHING PRE DISCHARGE RUN PROGRAM SCROLL DOWN TBL SUP ACKNOWLEDGE SIGNAL SILENCE SYSTEM RESET SCROLL UP TBL SUP ACKNOWLEDGE VIEWING ANGLE RED OUTPUT LED STEADY ABORT SET SELECT FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS N 120 LAMP TEST RELEASING SERVICE SIGNAL SILENCE HOLD FOR 2 SECONDS See page 83 for smoke detector compatibility data See pages 17 19 fo...

Страница 74: ...2 The panel is completely programmed except for the custom banner and zone messages Move the program switch back up PROGRAM 23 ZONES SUPERVISORY 2 1 2 3 4 OUTPUTS Supervisory Detection Detection Detection Detection 1 ALARM INDICATING X X X X 2 TROUBLE 3 SUPERVISORY X 4 RELEASE X X X X SUP 1 defaults to abort OPERATION DESCRIPTION Description Single Hazard 4 detection zones mapped to 1 release Inpu...

Страница 75: ...IONAL CA2Z MOUNTING LOCATION ZONE 1 HEAT OR SMOKE DETECTORS ZONE 2 HEAT OR SMOKE DETECTORS ZONE 3 HEAT OR SMOKE DETECTORS ZONE 4 HEAT OR SMOKE DETECTORS 5 1K EOLR RED BLACK 5 1K EOLR RED BLACK 5 1K EOLR RED BLACK N 120 RELEASING SERVICE SIGNAL SILENCE SIMULTANEOUS PRESS FOR 2 SECONDS ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS LAMP TEST RELEASING SERVICE SIGNAL SILENCE HOLD FOR 2 SECONDS Wiring Diagr...

Страница 76: ...s completely programmed except for the custom banner and zone messages Move the program switch back up PROGRAM 24 ZONES SUPERVISORY 2 1 2 3 4 OUTPUTS Supervisory Detection Detection Manual Release Low Air 1 ALARM INDICATING X X 2 ALARM INDICATING X 3 RELEASE X X X 4 SUPERVISORY X X SUP 1 defaults to abort OPERATION DESCRIPTION Description Single Hazard 2 detection zones a manual station zone and a...

Страница 77: ...RY 2 COMMON ALARM SIGNAL SILENCE STEADY DISCHARGE FLASHING PRE DISCHARGE RUN PROGRAM SCROLL DOWN TBL SUP ACKNOWLEDGE SIGNAL SILENCE SYSTEM RESET SCROLL UP TBL SUP ACKNOWLEDGE VIEWING ANGLE RED OUTPUT LED STEADY ABORT SET SELECT FUNCTION ALM SIGNAL ACTIVATION HOLD FOR 2 SECONDS N 120 LAMP TEST RELEASING SERVICE SIGNAL SILENCE HOLD FOR 2 SECONDS See page 83 for smoke detector compatibility data See ...

Страница 78: ... Linear Heat Detection Low Air Manual Release High Air Firecycle Zone 1 only Low Air Alarm Describe Initiating dedicated Supervisory Zone Sup 1 Sup 2 Supervisory Tamper Low Air High Air Select Soak Timer Describe Output Zones Alarm Indicating Releasing Supervisory Bell Trouble Bell 1 Releasing circuits normal cross zoned 2 Discharge time 7 8 9 10 20 minutes or continuous Map Alarm Inputs to Output...

Страница 79: ...ble interlock system Usually cross zoned with a smoke or heat detector Activation of this zone creates a supervisory condition on the panel but can still operate the release circuit 7 SUPERVISORY For monitoring any supervisory function as assigned 8 TAMPER For control valve monitoring 9 LOW AIR Used to detect low air pressure 10 HIGH AIR Used to detect high air pressure The first five descriptions...

Страница 80: ...o the next function the following will appear in the display window Output Description This allows the user to describe the functions of the output circuits Four descriptions are available 1 ALARM INDICATING Notification appliances include bells horns strobes and other appliances used to indicate an alarm 2 RELEASING Releasing appliances include solenoids and other electrically compatible devices ...

Страница 81: ...LARM INDICATING can be mapped to any initiating zones that were described as alarm zones including zones programmed as LOW AIR ALARM Any initiating zone that was described as supervisory will automatically be mapped to outputs described as SUPERVISORY BELL including zones programmed as LOW AIR ALARM The V is pointing to the first available output for the zone indicated on the display If the output...

Страница 82: ...ed the following will appear in the display window The is pointing to the first character on the top line Press the SET button to scroll one direction through the character set or press the SELECT button to scroll the other direction The entire alphabet numbers and punctuation are included SET Press the SET button to scroll through the character set in one direction SELECT Press the SELECT button ...

Страница 83: ...witch used in a double interlock system Usually cross zoned with a smoke or heat detector Activation of this zone creates a supervisory condition on the panel but can still operate the release circuit 6 SUPERVISORY For monitoring any supervisory function as assigned 7 TAMPER For control valve monitoring 8 LOW AIR Used to detect low air pressure 9 HIGH AIR Used to detect high air pressure The first...

Страница 84: ... include bells horns strobes and other appliances used to indicate an alarm These outputs are also programmable as first or second alarm when in chemical mode The outputs programmed as first alarm will activate continuously upon activation of any alarm zone mapped to that output Outputs programmed as second alarm will continue to operate in a continuous mode 2 RELEASING Releasing appliances includ...

Страница 85: ...NCTION the following will be displayed if any outputs have been described as RELEASING Where a is the number of the releasing circuit output Normal Cross Zoning Each releasing circuit can be set up for the normal or cross zoned operation In NORMAL operation any alarm initiating zone including LOW AIR ALARM mapped to a releasing output must be in alarm before the output is activated In cross zoned ...

Страница 86: ...de only functions if the release circuit is cross zoned The IRI mode has the same functions as the ULI mode except the abort button must be pressed and held before the second zone necessary for the activation of the release circuit goes into alarm Activation of the abort after the second alarm is received will have no effect If the release circuit is not cross zoned operation of the abort circuit ...

Страница 87: ... is turned on for that zone If the number is not displayed it is turned off If an output is not available for that zone i e SUPERVISORY BELL the v will skip to the next available output SET Press the SET button to set the output to the zone displayed and move to the next available output SELECT Press the SELECT button to turn the output either on or off the output number will be displayed when tur...

Страница 88: ...scroll through the numbers FUNCTION Press the FUNCTION button to skip this function When finished with this section the following will appear in the display window Quit by returning the programming switch to the RUN position The panel is now ready for operation Programming Summary Examine History Buffer Set Time Enter Password Enable Disable Initiating Zones Enable Disable Output Zones System Mode...

Страница 89: ...er Zone Is 25 Det Model Identifier Base Model Identifier 611U S10 601U S00 611UD S10 601U S00 611UT S10 601U S00 612U S10 601U S00 612UD S10 601U S00 613U5 S10 601U S00 611UD S10 609U10 S00 612UD S10 609U10 S00 425C S10 N A N A 425CT S10 N A N A Hochiki Max No Of Detectors Per Zone Is 25 Det Model Identifier Base Model Identifier SLR 24 HD 3 HSC 221R HB 71 HSB 221 HB 54 HSB 221N HB 54 NS6 221 NS4 ...

Страница 90: ...l of the above Fenwal detectors and bases can be used in any combination Retrofit Base Adaptor 70 501000 003 Identifier MAFE1 for series 70 201000 Bases Models 001 002 003 and 005 Duct Housing with Detector Base DH 51 Identifier DH22FE5 for CPD 7051 and PSD 7155 detectors only Potter Max No Of Detectors Per Zone Is 25 Det Model Identifier Base Model Identifier PS 24 HD 3 HOCHIKI SB 46 HB 71 HOCHIK...

Страница 91: ...91 VFR 400 5403548 REV W 8 17 4 WIRE HEAT DETECTOR COMPATIBILITY IDENTIFIER A Viking Firecycle normally closed heat detectors ...

Страница 92: ...ic 0 50 System Sensor B112LP Base 0 12 36 System Sensor B114LP Base System Sensor B404B Base System Sensor DH100ACDC Photoelectric 0 15 0 70 System Sensor DH100ACDCLP Photoelectric 0 15 0 70 System Sensor DH100ACDCLWP Photoelectric 0 15 0 70 System Sensor DH400ACDCI Ionization Duct 25 95 System Sensor DH400ACDCP Photoelectric Duct 25 95 System Sensor 1112 24 D Ionization 0 05 50 System Sensor 1424...

Страница 93: ...23 System Sensor 4WTA B 12 24V I Photo w therm sounder 05 35 System Sensor 4WTR B 12 24V I Photo w therm relay 05 35 System Sensor 4WTAR B 12 24V I Photo w therm sounder relay 05 50 System Sensor 4WITAR B 12 24V I Photo w isolated therm sounder relay 05 50 System Sensor 2WMOD2 I Loop test maint mod 05 System Sensor RRS MOD I Reversing relay sync module 05 System Sensor 6424 Projected beam 10 28 4 ...

Страница 94: ...C Fire Control Releasing Panel to convert from two Class B initiating device circuits to two Class A circuits UL Listed Option for use with the PFC 4410RC Series Transient Protected Built In 5 1k End Of Line Resistor PC Board Assembly Mounts to PFC 4410RC Panel stand offs Stock No 3006013 PotterElectricSignalCompany LLC St Louis MO CustService 866 572 3005 TechSupport 866 956 0988 Canada888 882 18...

Страница 95: ...uilt in polarized 5 1k end of line resistor TERMINAL BAR CAM MODULE NO 1 CAM MODULE NO 2 IF USED 5 1 2 1 2 1 2 BATTERY BATTERY CAM EXTERNAL INDICATING APPLIANCES DWG 927 15 TO INDICATING APPLIANCE CIRCUIT TERMINALS POLARITY SHOWN IS FOR ALARM CONDITION REMOVE EOL RESISTOR BLACK RED 1 2 3 4 MFG 5400927 REV L 9 08 PRINTED IN USA PAGE 1 OF 1 PotterElectricSignalCompany LLC St Louis MO CustService 866...

Страница 96: ...tivated PAGE 1 OF 1 PRINTED IN USA Wiring Placement In PFC 4410RC Series Control Unit PotterElectricSignalCompany LLC St Louis MO CustService 866 572 3005 TechSupport 866 956 0988 Canada888 882 1833 www pottersignal com 18 WIRE LEADS FURNISHED FOR RELAY COIL RED BLACK 7 8 RELAY SHOWN DE ENERGIZED NUMBERS REFER TO SOCKET TERMINALS NOT RELAY PINS 1 5 3 2 6 4 FOURTH RELAY FOR PFC 4410 DWG 977 1 MAIN ...

Страница 97: ...al circuit current available The ARM 1 Auxiliary Relay Module is a non supervised 4PDT Relay CONNECT ARM 1 TO OUTPUT CIRCUIT RED BLACK PFC 4410RC OUTPUT TERMINALS DWG 1134 2 1 9 5 2 10 6 3 11 7 4 12 8 All relays shown in non activated condition ARM 1 PFC 4410RC Installation Hook Up Diagram Notes 1 Numbers refer to socket terminals not relay pins 2 Auxiliary relay operation is determined by program...

Страница 98: ...98 VFR 400 5403548 REV W 8 17 ...

Страница 99: ...99 VFR 400 5403548 REV W 8 17 ...

Отзывы: