![Viking VFR400 Скачать руководство пользователя страница 48](http://html.mh-extra.com/html/viking/vfr400/vfr400_manual_1023432048.webp)
48
VFR-400 • 5403548 • REV W • 8/17
XX = Cross-Zoned
NOTES
:
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (Release
Solenoid). Black wire to negative terminal on panel and Red wire through Solenoid to positive terminal on panel.
2. Polarity is shown on indicating circuits in an activated (in alarm) condition.
3. Leave EOLR (provided) on all unnused circuits.
4. See the instruction manual for circuit information, panel limits, and battery sizing.
5. For wire routing instructions through the releasing panel, see Note 3 on page 20 of the instruction manual.
6. See instruction manual for proper programming.
7. See instruction manual for list of compatible smoke detectors.
8. See specific system type data page for proper pressure switch settings.
9. Loss of DC power below 20 volt causes output #3 (Release Solenoid) and output #4 (N/O Solenoid) to drop out.
10. See Viking technical data sheet F_051704 for Surefire double interlock operation.
PROGRAM #11
For One Sprinkler System
Viking Sprinkler
System Types
2 Cross Release
Zones and Manual
Release Zone
1. SUREFIRE Double Interlocked Preaction System
2. SUREFIRE Double Interlocked Preaction System - NYC Special
3. SUREFIRE Double Interlocked Preprimed Preaction System
4. SUREFIRE Double Interlocked Preprimed Preaction System - NYC Special
OUTPUTS
(Indicating Circuits)
ZONES (Initiating Circuits)
SUP 1
SUP 2
#1
#2
#3
#4
Valve Tamper
Supervisory Zone
Low Air
Supervisory Zone
Conventional
Detection Zone
Low Air Alarm
Zone
Waterflow
Zone
Manual
Release Zone
#1 General Alarm
X
X
X
#2 Supervisory Bell
X
X
X
#3 Release Solenoid
X X
X X
X
#4 N/O Solenoid
X
OPERATION DESCRIPTION
Inputs:
1 Conventional Detection zone, 1 Low Air Alarm zone, 1 Waterflow zone, 1 Manual Release zone, 2
Supervisory zones
Outputs:
1 General Alarm, 1 Supervisory Bell, 1 Release Solenoid, 1 N/O Solenoid
Operation:
Simultaneous activation of both the Conventional Detection zone #1 and the Low Air Alarm zone #2
will activate output #3 (Release Solenoid), output #1 (General Alarm), and output #4 (N/O Solenoid)
Activation of Conventional Detection zone #1 will activate output #1 (General Alarm)
Activation of Low Air Alarm zone #2 will activate output #2 (Supervisory Bell) and output #4 (N/O
Solenoid)
Activation of Waterflow zone #3 will activate output #1 (General Alarm)
Activation of Valve Tamper Supervisory zone #1 or Low Air Supervisory zone #2 will activate
output#2 (Supervisory Bell)
Activation of Manual Release zone #4 will activate output #3 (Release Solenoid) and output #1
(General Alarm)
A trouble condition will prevent output #4 (N/O Solenoid) from activating