63
VFR-400 • 5403548 • REV W • 8/17
N
L
HOT - BLACK
NEUTRAL - WHITE
EARTH GROUND - GREEN
OUTPUT 1
BAT+
ASSY
DIODE
EOL
RE
D
BLAC
K
NO
COM
NC
NC
NO
NO
NO
COM
COM
COM
BLAC
K
RE
D
5.1K
EOLR
BLAC
K
RE
D
EOLR
5.1K
BLAC
K
RE
D
RELEASE
ALARM
GENERAL
SOLENOID
ZONE 4
RELEASE
STATION
WATER
FLOW
ZONE 3
SWITCH
ZONE 2
ZONE 1
DETECTION
CONVENTIONAL
SUP 2
SUP 1
DRY CONTACTS RATED AT 3A, 30VDC
TROUBLE
SUPV
RELAY CONTACTS
ALARM
EOLR
5.1K
SUPERVISORY
BELL
WATERFLOW
AUX. POWER
RS-485
24 VNR DC
120 OHM
VALVE
TAMPER
SUPERVISORY
LOW AIR
PRESSURE
SUPERVISORY
SWITCH
09472
24VR DC
WTRFLW
09470
ZONE 1
ZONE 2
ZONE 3
ZONE 4
OUTPUT 1
OUTPUT 2
OUTPUT 3
OUTPUT 4
POWER TBL
SYSTEM TBL
FAULT
SUPERVISORY 2
COMMON ALARM
SILENCE
STEADY: DISCHARG
FLASHING: PRE-
DISCHARGE
E
SCROLL-DOWN
SYSTEM RESET
SCROLL-UP
VIEWING ANGLE
EOLR
5.1K
EOLR
5.1K
EOLR
5.1K
EOLR
5.1K
BAT-
OUTPUT 2
OUTPUT 3
OUTPUT 4
MANUAL
ZONE 1
DETECTION
CONVENTIONAL
ZONE 2
EOLR
5.1K
BLAC
K
RE
D
EOLR
5.1K
SUPERVISORY 1
}
}
21
2
1
POWER ON
SIGNAL
(SELECT)
SIGNAL SILENCE
RELEASING
SERVICE SIGNAL
SILENCE HOLD
FOR 2 SECONDS
LAMP TEST
(SET)
RUN
(PROGRAM)
(FUNCTION)
ALM SIGNAL
ACTIVATION HOLD
FOR 2 SECONDS
EARTH
SUP/ABORT TBL
TBL/SUP
ACKNOWLEDGE
TBL/SUP
ACKNOWLEDGE
DWG# 14184 VKG PRGM18
1. Run field wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory
installed EOLR on all unused circuits.
2. Connect one circuit at a time and apply AC power.
3. Connect batteries to the panel.
4. Once last connection is made, move Program switch down.
5. Press the FUNCTION button until the display reads “PASSWORD = 000”.
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET
button to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000
password.)
7. Press the FUNCTION button until the display reads “PROGRAM #18”.
8. Press the SELECT button until the display reads “PROGRAM #18”.
9. Press the SET button.
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.
S
N.O. Initiating Device
Conventional Detection
Notification Appliance
Solenoid
End-of-Line Diode Assy
Legend
PROGRAM #18
Note: Release solenoids #1 and #2 shall be wired in parallel and connected to output #3. the wiring shall be in conduit or
otherwise protected. Any connections shall be made in a junction box. This may not conform to the monitoring for integrity
requirements for NFPA 72.