VFR-400 • 5403548 • REV W • 8/17
NOTES
:
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #2 (Release Solenoid) and output #3 (Release
Solenoid). Black wire to negative terminal on panel and Red wire through Solenoid to positive terminal on panel.
2. Polarity is shown on indicating circuits in an activated (in alarm) condition.
3. Leave EOLR (provided) on all unnused circuits.
4. See the instruction manual for circuit information, panel limits, and battery sizing.
5. For wire routing instructions through the releasing panel, see Note 3 on page 20 of the instruction manual.
6. See instruction manual for proper programming.
7. See instruction manual for list of compatible smoke detectors.
8. See specific system type data page for proper pressure switch settings.
PROGRAM #5
For One Sprinkler System- NYC Special
Viking Sprinkler
System Types
Release Zone and
Manual Release
Zone
1. Single Interlocked Preaction System with Electric Release
2. Deluge System with Electric Release
3. Non-Interlocked Preaction with Electric Release
4. Double Interlocked Preaction System with Electric/Pneumatic Release
OUTPUTS
(Indicating Circuits)
ZONES (Initiating Circuits)
SUP 1
SUP 2
#1
#2
#3
#4
Valve Tamper
Supervisory Zone
Low Air
Supervisory Zone
Conventional
Detection Zone
Low Air Alarm
Zone
Waterflow
Zone
Manual
Release Zone
#1 General Alarm
X
X
X
#2 Supervisory Bell
X
X
X
#3 Release Solenoid
X
X
#4 Trouble Bell
OPERATION DESCRIPTION
Inputs:
1 Conventional Detection zone, 1 Waterflow zone, 1 Low Air Alarm zone, 1 Manual Release zone, 2
Superviosry zones
Outputs:
1 General Alarm, 1 Trouble Bell, 1 Release Solenoid, 1 Supervisory Bell
Operation:
Activation of Conventional Detection zone #1 or Manual Release zone #4 will activate output #3
(Release Solenoid) and output #1 (General Alarm)
Activation of Waterflow zone #3 will activate output #1 (General Alarm)
Activation of Low Air Alarm zone #2 or Low Air Supervisory zone or Valve Tamper Supervisory zone
will activate output #2 (Supervisory Bell)
A trouble condition, (low battery, wire short in outputs, loss AC, panel problem) will activate output
#4 (Trouble Bell) and trouble relay