56
VFR-400 • 5403548 • REV W • 8/17
PROGRAM #15
For One Sprinkler System
Viking Sprinkler System
Types
(UK only)
2 Release Zones,
Waterflow Zone,
and Manual Release
Zone
E-1 Single-interlocked Surefire preaction system with Electric-Pneumatic
release
OUTPUTS
(Indicating Circuits)
ZONES (Initiating Circuits)
SUP 1
SUP 2
#1
#2
#3
#4
Valve Tamper
Supervisory Zone
Low Air
Supervisory
Zone
Conventional
Detection
Zone
Low Air
Alarm Zone
Waterflow
Zone
Manual
Release
Zone
#1 General Alarm
X
X
X
#2 Low air/Tamper
X
X
X
#3 Release Solenoids #1 & #2
X
X
#4 N/O Solenoid
X
OPERATION DESCRIPTION
Inputs:
1 Conventional Detection zone, 1 Low air alarm zone, 1 Waterflow zone, 1 Manual Release
zone, 2 Supervisory zones
Outputs:
1 General Alarm, 1 Low Air/Tamper, 2 Release Solenoids (single output from panel), 1 N/O
solenoid
Operation:
Activation of Conventional Detection zone #1 or manual release zone #3 will activate output
#3 (release solenoids) and output #1 (General Alarm)
Activation of Low Air Alarm zone #2 will activate output #2 Low air/tamper and output #4
(N/O solenoid)
Activation of Waterflow zone #3 will activate output #1 (General Alarm)
Activation of Valve Tamper supervisory zone #1, Low air supervisory zone #2, or Low Air
alarm zone #2 will activate output #2 (Low Air/Tamper)
A trouble condition will prevent output #4 (N/O) from activating
NOTES
:
1. Connect EOL Diode assembly IN SERIES as shown with solenoids on outputs #3 and #4. Black wire to negative terminal on
panel. Red wire through solenoid to positive terminal on panel. Output #3 has 2 solenoids. These must be connected in parallel
and the EOL diode is connected in series with the parallel solenoids.
2. Polarity is shown on indicating/release circuits in an activated (in alarm) condition.
3. Leave EOLR (provided) on all unnused circuits.
4. See the instruction manual for circuit information, panel limits, and battery sizing.
5. For wire routing instructions through the releasing panel, see Note 3 on page 20 of the instruction manual.
6. See instruction manual for proper programming.
7. See instruction manual for list of compatible smoke detectors and solenoids.
8. See specific system type data page for proper pressure switch settings.
9. Loss of power below 20 volts causes output #3 (release solenoids) and output #4 (N/O solenoid) to drop out.
10. See Viking technical data sheet F_051604 for Surefire single interlock operation.
11. For UL864 Approved Programming Options, see page 5.