![Viking VFR400 Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/viking/vfr400/vfr400_manual_1023432018.webp)
18
VFR-400 • 5403548 • REV W • 8/17
1. To measure the battery charging voltage:
Place a voltmeter across the battery terminals as shown in FIG. 4
2. To measure the battery charging current:
Place a current meter in series with the battery terminals as shown in FIG. 5.
DWG# 3527-9
VOLT
METER
CURRENT
METER
PANEL
PANEL
CONNECTION PROCEDURE FOR BATTERY CHARGING CURRENT AND VOLTAGE
CONNECTION DRAWING FOR CENTRAL STATION OPERATION OF VFR-400 TO ANY UL LISTED
DACT
E.O.L.
BATTERY
- +
PLINK
A- A+
- +
- +
- +
A B
AUX
NAC
POTS DACT CONNECTION
ALARM SIGNAL ACTIVATION
PRESS LEFT & RIGHT
ARROW KEYS AT SAME
TIME TO TRIGGER ALARM
SIGNAL ACTIVATION.
LAMP TEST: PRESS [ENTER], [5],
PASSWORD, [6]. PRESS THE [ESC] KEY
WHEN DONE.
GROUND
F
U
S
E
BLACK
WHITE
INPUT3
- +
B- B+
INPUT4
INPUT5
INPUT6
- +
- +
- +
INPUT2
INPUT1
- +
Line2 In
Line2 Out Line1 In
Line1 Out
Tip Ring Tip Ring Tip Ring Tip Ring
FUSE
ONLY DETECTORS THAT ARE SHOWN IN
THE COMPATIBILITY LIST ARE TO BE USED.
1
2
3
4
5
6
7
8
0
ESC
ENTER
POWER ON
EARTH FAULT
ALARM
SUPERVISORY
TROUBLE
SILENCED
FIRE
DRILL
ACK
NOWLEDGE
SIGNAL
SILENCE
RESET
9
RELAY
TERMINALS
ROTARY SWITCH
ROTARY SWITCH
ARM-44
SET TO MODE 2
VFR-400 RS-485 CONNECTION
COM
NO
NC
COM
NO
NC
+
-
+
S
-
+
-
+
S
-
24VDC RS-485
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
ZONE1/ZONE1/SUP | ZONE 2/ ZONE2/TBL ZONE3/ZONE3/ALM | ZONE4/ZONE4/ALM OUT1/SUP/OUT1 | OUT2/TBL/OUT2 OUT3/ALM/OUT3 | OUT4/ALM/OUT4
DISABLE
LA
TC
H
MODE
2
MODE
3
ALL
OUTPUTS DISABLED
ALL
OUTPUTS LA
TCHING
MODE 2 OPERA
TION
MODE 3 OPERA
TION
MODE 1 = MODE
2&3 OF
F
ON
OFF
1
2
4
3
0
5
6
7 8
9
S
-
-
+
+
PFC-6006
UL Listed
DACT
CONNECT THE DRAIN WIRE TO THE S TERMINAL OF
THE VFR-400 ONLY. DO NOT CONNECT THE DRAIN
WIRE TO THE ARM-44. CUT THE DRAIN WIRE OFF AT
THE ARM-44 AND INSULATE IT. IF MORE THAN ONE
DEVICE IS CONNECTED TO THE RS 485 CIRCUIT, THE
DRAIN WIRE MUST BE SPLICED TOGETHER TO
MAKE A CONTINUOUS PATH TO THE LAST DEVICE
WHERE IT IS CUT OFF AND INSULATED.
REMOVE THE 120R RESISTOR FROM THE VFR-400
PANEL AND INSTALL ON THE LAST DEVICE ONLY.
REMOVE THE RESISTOR
FROM THE VFR-400 AND
INSTALL ON THE LAST
DEVICE ONLY.
120 OHM RESISTOR -
ANNUNCIATOR SELECTOR
SWITCH SET FOR THE TOTAL
NUMBER OF DEVICES INSTALLED
ON THE RS-485 TERMINALS