![Viking VFR400 Скачать руководство пользователя страница 8](http://html.mh-extra.com/html/viking/vfr400/vfr400_manual_1023432008.webp)
8
VFR-400 • 5403548 • REV W • 8/17
LCD
A 2 line 32 character alpha-numeric liquid crystal display shows the condition, status and circuit for all
Alarm, Supervisory and Trouble conditions:
CONDITION
STATUS
CIRCUIT
Alarm
<user Defined Message> (Up To 10 Characters)
Trouble
Disabled
Output #1
Supervisory
Acknowledged
Output #2
Tamper Silenced
Output #3
Low Air
Output #4
High Air
Battery
A.C.
Pre-discharging
Supervisory
Releasing
Zone #1
Released
Zone #2
Zone #3
Zone #4
Ground
VFR-400 Visual Indicators
In accordance with ULC S527 option B:
LED Annunciator Module
Red LED’s:
Initiating Device Circuits Active (4),
Notification/Release Circuits Active (4)
Pre-Discharge/Discharge
Common Alarm (1)
Green LED: POWER ON
Yellow LED’s: Initiating Device Circuits Troubles (4),
Output Circuits Troubles (4)
Supervisory Initiating Zone (4)
Supervisory Bell Output Active (4)
(1) each: Supervisory 1/Abort: Supervisory 2, Power Trouble, Supervisory/Abort Trouble, System Trouble,
Earth Fault, Signal Silenced
CONDITION
STATUS LED State
Trouble
Non-Silenced
Flashing
Trouble
Silenced
Steady ON
Alarm
Non-Silenced Flashing
Alarm
Silenced
Steady ON
Supervisory
Non-Silenced Flashing
Supervisory
Silenced Steady ON
Pre-discharge
Flashing
Discharging
Steady ON
Control Buttons
• Signal Silence - Momentary, silences signaling circuits, (except those activated by zones programmed as WATERFLOW)
• System Reset - Momentary, resets all alarm circuits if condition has been corrected, removes power from initiating device cir
-
cuits.
• Scroll Up - Scrolls LCD display to most recent events
• Scroll Down - Scrolls LCD display to previous event
• Alarm Signal Activation - Simultaneous press SCROLL-UP and SIGNAL SILENCE to sound or re-sound the Alarm
indicators.
• Releasing Service Signal Silence - Simultaneous press SCROLL-DOWN and SIGNAL SILENCE to Silence Outputs
designated as 2nd Alarm.
NOTE
:
TBL/SUP ACKNOWLEDGE is accomplished by scrolling through all events.
Содержание VFR400
Страница 67: ...67 VFR 400 5403548 REV W 8 17 This page intentionally left blank ...
Страница 98: ...98 VFR 400 5403548 REV W 8 17 ...