84
VFR-400 • 5403548 • REV W • 8/17
Zone 5 is a supervisory or abort zone and can only be described as SUPERVISORY, TAMPER, LOW AIR or HIGH AIR, or ABORT.
SET
Press the SET button to set the description displayed.
SELECT
Press the SELECT button to scroll through the four supervisory and abort descriptions.
FUNCTION
Press the FUNCTION button to skip to the next function.
Zone 6 is a supervisory zone and can only be described as SUPERVISORY, TAMPER, LOW AIR or HIGH AIR.
SET
Press the SET button to set the description displayed.
SELECT
Press the SELECT button to scroll through the four supervisory and abort descriptions.
FUNCTION
Press the FUNCTION button to skip to the next function.
After describing what the supervisory zone is to be or skipping to the next function, the following will appear in the display window:
Output Description
This allows the user to describe the functions of the output circuits and whether they indicate first or second alarm, or release
activated. Four descriptions are available:
1) ALARM INDICATING - Indicating appliances include bells, horns, strobes and other appliances used to indicate an alarm.
These outputs are also programmable as first or second alarm when in chemical mode. The outputs programmed as first alarm
will activate continuously upon activation of any alarm zone mapped to that output. Outputs programmed as second alarm will
continue to operate in a continuous mode.
2) RELEASING - Releasing appliances include solenoids and other electrically compatible devices.
3) SUPERVISORY BELL - Appliances on this circuit are used to indicate the presence of a supervisory condition. Any zone
programmed as LOW AIR ALARM, SUPERVISORY, TAMPER, HIGH AIR or LOW AIR is automatically mapped to this output.
4) TROUBLE BELL - Appliances on this circuit are used to indicate the presence of a trouble condition. The user should describe
each output circuit in the same manner as the initiating circuit was described by pressing the middle button to select and the top
button to set the desired function.
SET
Press the SET button to set the description displayed.
SELECT
Press the SELECT button to scroll through the descriptions.
FUNCTION
Press the FUNCTION button to skip to the next function.
S U P
E
R V S R Y
2
Z
O N
E
S U P
E
R V I S R Y
O U T P U T
# 1
I N
D
I C A T I N
G