VFR-400 • 5403548 • REV W • 8/17
The next function will be displayed as follows:
Releasing Output Time
This allows the user to determine how long the releasing circuit is energized upon alarm. The available
times are 7, 8, 9, 10, 20 minutes and continuous. Use the middle button to scroll through the possible
options and the top button to set that option. Press the bottom button to skip to the next function.
SET
Press the SET button to set the time displayed.
SELECT
Press the SELECT button to scroll through the available time.
FUNCTION
Press the FUNCTION button to skip to the next function.
After a discharge time is entered, a display similar to the following will appear:
This display is where the outputs are mapped to the initiating zones. Any output that was previously described as “RELEASING”
or “ALARM INDICATING” can be mapped to any initiating zones that were described as alarm zones, including zones
programmed as LOW AIR ALARM. Any initiating zone that was described as supervisory will automatically be mapped to
outputs described as “SUPERVISORY BELL”, including zones programmed as LOW AIR ALARM. The “v” is pointing to the
first available output for the zone indicated on the display. If the output number is displayed, it is turned on for that zone. If the
number is not displayed, it is turned off. If an output is not available for that zone, i.e. “SUPERVISORY BELL”, the “v” will skip
to the next available output.
SET
Press the SET button to set the output to the zone displayed and move to the next available
output.
SELECT
Press the SELECT button to turn the output either on or off (the output number will be displayed when turned on).
FUNCTION
Press the FUNCTION button to skip to the next function.
After all available outputs for the zone displayed are mapped, the display will automatically change to the next zone.
After mapping the last zone or skipping to the next function, the following will appear in the display window:
D
I S C
H
A R
G E
T I M
E
C O N T I N U O U S
Z
O N
E
1
V
O U T P U T S :
1
2
3
4
B A N N
E
R
M
E
S S A
G E ?
C U S T O M
M
E
S S A
G E
*
The abort zone is a non-latching zone. In order for the abort function to operate, the abort button must be pressed and held
continuously. Releasing the abort button will continue the pre-discharge timer.
*
The abort function will not prevent the activation of the release circuit if a zone programmed as MANUAL RELEASE has
been activated. MANUAL RELEASE always overrides the abort function.
*
The abort function will not prevent the activation of the release circuit if there is no pre-discharge time set or if the pre-
discharge time is 1 second or less when the abort button is pressed.