VFR-400 • 5403548 • REV W • 8/17
PROGRAM #9
For One Sprinkler System
Viking Sprinkler
System Types
1 Release Zone
and Manual
Release Zone
1. FIRECYCLE III Wet Multicycle System
OUTPUTS
(Indicating Circuits)
ZONES (Initiating Circuits)
SUP 1
SUP 2
#1
#2
#3
#4
Supervisory Zone
Valve Tamper
Supervisory Zone
FIRECYCLE
Detector Zone
Supervisory
Zone
Waterflow
Zone
Manual
Release Zone
#1 General Alarm
X
X
X
#2 Supervisory Bell
X
X
X
#3 Release Solenoid
X
X
#4 N/O Solenoid
X
X
OPERATION DESCRIPTION
Inputs:
1 FIRECYCLE Detection zone, 1 Supervisory zone, 1 Waterflow zone, 1 Manual Release zone, 2
Supervisory zones
Outputs:
1 General Alarm, 1 Supervisory Bell, 1 Release Solenoid, and 1 N/O Solenoid
Operation:
Activation of FIRECYCLE Detector zone #1 will activate output #1 (General Alarm), output #3 (Release
Solenoid) and output #4 (N/O Solenoid)
Activation of Supervisory zone #2 will activate output #2 (Supervisory Bell)
Activation of Waterflow Alarm zone #3 will activate output #1 (General Alarm) and output #4 (N/O
Solenoid)
Activation of Manual Release zone #4 will activate output #1 (General Alarm) and output #3 (Release
Solenoid)
Deactivation of FIRECYCLE Detector zone #1 will start soak timer, when timer cycle is complete the
output #3 (Release Solenoid) is deactivated.
Activation of Supervisory zone #1 or Valve Tamper Supervisory zone #2 will activate output #2
(Supervisory Bell)
NOTES
:
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (N/O
Solenoid). Black wire to negative terminal on panel and Red wire through Solenoid to positive terminal on panel.
2. Polarity is shown on indicating circuits in an activated (in alarm) condition.
3. Leave EOLR (provided) on all unnused circuits.
4. See the instruction manual for circuit information, panel limits, and battery sizing.
5. For wire routing instructions through the releasing panel, see Note 3 on page 20 of the instruction manual.
6. See instruction manual for proper programming.
7. See specific system type data page for proper pressure switch settings.
8. Connect EOL resistor after last FIRECYCLE detector on return line to common terminal in FIRECYCLE Detector zone #1.
9. Set the soak timer to desired duration period. Factory setting is continuous. Recommend 60 seconds minimum.
10. Loss of DC power below 20 volt causes output #3 (Release Solenoid) and output #4 (N/O Solenoid) to drop out.
11. Use only Viking FIRECYCLE detectors on FIRECYCLE Detector zone #1.
12. Refer to Viking technical data sheet F_051504 for Firecycle multi-cycle wet system operation.
13. For UL864 Approved Programming Options, see page 5.