Coding in the delivered condition
Possible change
51:0
Internal circulation
pump is always started
when there is a heat de-
mand
51:1
When there is a heat de-
mand, the internal circu-
lation pump will only be
started when the burner
is operational. System
with heating water buffer
cylinder.
52:0
Without flow tempera-
ture sensor for low loss
header
52:1
With flow temperature
sensor for low loss head-
er (automatic adjustment
on connection)
53:1
Function connection
sK
of the internal exten-
sion: DHW circulation
pump
53:0
Function connection
sK
:
Central fault
53:2
Function connection
sK
:
External heating circuit
pump (heating circuit A1)
53:3
Function connection
sK
:
External circulation pump
for cylinder heating
54:0
Without solar control
unit
54:1
With Vitosolic 100 (auto-
matic adjustment on con-
nection)
54:2
With Vitosolic 200 (auto-
matic adjustment on con-
nection)
DHW
56:0
Set DHW temperature
adjustable from 10 to
60 °C
56:1
Set DHW temperature
adjustable from 10 to
above 60 °C
Note
Maximum value subject
to boiler coding card.
Observe the max. per-
missible DHW tempera-
ture.
58:0
Without auxiliary func-
tion for DHW heating
58:10
to
58:60
Input of a second set
DHW temperature, adjus-
table from 10 to 60 °C
(observe coding ad-
dresses "56" and "63")
Code 2
(cont.)
46
Coding
5692
673
GB
Содержание VITODENS 300-W
Страница 106: ...aND Water pressure sensor a Modulation coil Connection and wiring diagram internal cont 106 Designs 5692 673 GB...
Страница 107: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 107 Designs 5692 673 GB...
Страница 111: ...Parts lists cont 111 Parts lists 5692 673 GB...
Страница 112: ...Parts lists cont 112 Parts lists 5692 673 GB...
Страница 113: ...Parts lists cont 113 Parts lists 5692 673 GB...
Страница 114: ...Parts lists cont 114 Parts lists 5692 673 GB...
Страница 121: ...121 5692 673 GB...
Страница 122: ...122 5692 673 GB...
Страница 123: ...123 5692 673 GB...