Air factor
λ
–
CO
2
/O
2
content
Air factor
λ
O
2
content
(%)
CO
2
content
(%) for natur-
al gas E
CO
2
content
(%) for natur-
al gas LL
CO
2
content
(%) for LPG P
1.24
4.4
9.2
9.1
10.9
1.27
4.9
9.0
8.9
10.6
1.30
5.3
8.7
8.6
10.3
1.34
5.7
8.5
8.4
10.0
1.37
6.1
8.3
8.2
9.8
1.40
6.5
8.1
8.0
9.6
1.44
6.9
7.8
7.7
9.3
To achieve an optimum combustion
control, the system regularly carries
out an automatic self-calibration; also
after a power failure (shutdown). For
this, the combustion is briefly regu-
lated to max. ionisation current
(equals air factor
λ
=1). The automatic
calibration is carried out shortly after
the burner start and lasts approx. 5 s.
During the calibration, higher than
normal CO emissions may occur
briefly.
The combustion control unit can also
be calibrated manually. e.g. after
maintenance or service work (coding
address "85").
Electronic combustion control unit
(cont.)
104
Function description
5692
673
GB
Содержание VITODENS 300-W
Страница 106: ...aND Water pressure sensor a Modulation coil Connection and wiring diagram internal cont 106 Designs 5692 673 GB...
Страница 107: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 107 Designs 5692 673 GB...
Страница 111: ...Parts lists cont 111 Parts lists 5692 673 GB...
Страница 112: ...Parts lists cont 112 Parts lists 5692 673 GB...
Страница 113: ...Parts lists cont 113 Parts lists 5692 673 GB...
Страница 114: ...Parts lists cont 114 Parts lists 5692 673 GB...
Страница 121: ...121 5692 673 GB...
Страница 122: ...122 5692 673 GB...
Страница 123: ...123 5692 673 GB...