Calling up fault codes from the fault memory (fault history)
The 10 most recent faults are saved
and may be scanned.
The faults are ordered by date, thus
the most recent fault is fault number 1.
Press the following keys:
1.
G
+
d
simultaneously for
approx. 2 s.
2.
a
/
b
for individual fault
codes.
3.
Note
All saved fault codes can be
deleted with
e
.
4.
d
Scanning is completed.
Fault codes
Fault
code
on the
display
Const.
weath.-
comp.
System char-
acteristics
Cause
Measures
0F
X
X
Control mode
Service
Service the equip-
ment. After the
service, set cod-
ing address
"24:0".
10
X
Regulates as
if the outside
temperature
was 0 °C
Outside tem-
perature
sensor
shorted out
Check the outside
temperature sen-
sor (see page 82).
18
X
Regulates as
if the outside
temperature
was 0 °C
Outside tem-
perature
sensor lead
broken
Check the outside
temperature sen-
sor (see page 82).
20
X
Regulates
without flow
temperature
sensor (low
loss header)
System flow
temperature
sensor
shorted out
Check the low
loss header sen-
sor (see page 83).
Fault display
(cont.)
71
Troubleshooting
5692
673
GB
Содержание VITODENS 300-W
Страница 106: ...aND Water pressure sensor a Modulation coil Connection and wiring diagram internal cont 106 Designs 5692 673 GB...
Страница 107: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 107 Designs 5692 673 GB...
Страница 111: ...Parts lists cont 111 Parts lists 5692 673 GB...
Страница 112: ...Parts lists cont 112 Parts lists 5692 673 GB...
Страница 113: ...Parts lists cont 113 Parts lists 5692 673 GB...
Страница 114: ...Parts lists cont 114 Parts lists 5692 673 GB...
Страница 121: ...121 5692 673 GB...
Страница 122: ...122 5692 673 GB...
Страница 123: ...123 5692 673 GB...