Coding in the delivered condition
Possible change
85:0
Standard mode
85:1
Manual calibration of the
combustion controller
(only adjustable if coding
address 11:9 has been
set).
The red fault indicator
also flashes during cali-
bration. The process has
terminated when the red
fault indicator no longer
flashes (after approx.
1 min).
Note
Heat must be drawn off
during manual calibra-
tion.
88:0
Temperature displayed
in °C (Celsius)
88:1
Temperature displayed in
°F (Fahrenheit)
8A:175
Never adjust
90:128
Time constant for calcu-
lating the adjusted out-
side temperature
21.3 hours
90:0
to
90:199
Fast (low values) or slow
(high values) matching of
the flow temperature,
subject to the set value
when the outside tem-
perature changes;
1 step
≙
10 min.
91:0
No external heating pro-
gram changeover via
external extension (only
for weather-compen-
sated control units)
91:1
The external heating pro-
gram changeover affects
the heating circuit without
mixer
91:2
The external heating pro-
gram changeover affects
the heating circuit with
mixer
91:3
The external heating pro-
gram changeover affects
the heating circuit without
mixer and the heating cir-
cuit with mixer
Code 2
(cont.)
50
Coding
5692
673
GB
Содержание VITODENS 300-W
Страница 106: ...aND Water pressure sensor a Modulation coil Connection and wiring diagram internal cont 106 Designs 5692 673 GB...
Страница 107: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 107 Designs 5692 673 GB...
Страница 111: ...Parts lists cont 111 Parts lists 5692 673 GB...
Страница 112: ...Parts lists cont 112 Parts lists 5692 673 GB...
Страница 113: ...Parts lists cont 113 Parts lists 5692 673 GB...
Страница 114: ...Parts lists cont 114 Parts lists 5692 673 GB...
Страница 121: ...121 5692 673 GB...
Страница 122: ...122 5692 673 GB...
Страница 123: ...123 5692 673 GB...