Gas type conversion (only for operation with LPG)
1.
Set adjusting screw
A
at the gas
train to "2".
2.
Switch ON system ON/OFF switch
"
8
".
3.
Adjust the gas type (see page
"82"):
&
Call up code 2
&
In coding address "11", select
value "9"
&
In coding address "82", select
value "1" (operation with LPG)
&
Set code "11"
≠
"9".
&
Terminate code 2.
4.
Open the gas shut-off valve.
Function sequence and possible faults
Display screen
Measures
Control unit is-
sues heat de-
mand
No
Increase set
value and ensure
heat is drawn off
Yes
Fan starts
No
after approx. 51 s
fault F9
Check the fan, fan
connecting
cables, power at
the fan and fan
control
Further details regarding the individual steps
(cont.)
12
Commissioning, inspection, maintenance
5692