Coding in the delivered condition
Possible change
F7:25
In "Standby mode", the
internal circulation
pump is permanently
ON (only for constant
temperature control
units)
F7:0
In "Standby mode", the
internal circulation pump
is permanently OFF
F7:1
to
F7:24
In "Standby mode", the
internal circulation pump
in operating mode will be
started for 10 min respec-
tively 1 to 24 times per
day.
F8:-5
Temperature limit for
terminating the reduced
mode -5 ºC, see exam-
ple on page 100.
Observe the setting of
coding address "A3".
(only for weather-com-
pensated control units)
F8:+10
to
F8:-60
Temperature limit adjus-
table from
+10 to -60 °C
F8:-61
Function disabled
F9:-14
Temperature limit for
raising the reduced set
room temp. -14 ºC, see
example on page 100.
(only for weather-com-
pensated control units)
F9:+10
to
F9:-60
Temperature limit for rais-
ing the set room tempera-
ture to the value selected
for standard mode adjus-
table from
+10 to -60 °C
FA:20
Raising the set boiler
water temperature or
the set flow temperature
when changing from op-
eration with reduced
room temperature to op-
eration with standard
room temperature, by
20 %. See example on
page 101 (only for
weather-compensated
control units).
FA:0
to
FA:50
Temperature rise adjusta-
ble from 0 to 50 %
Code 2
(cont.)
59
Coding
5692
673
GB
Содержание VITODENS 300-W
Страница 106: ...aND Water pressure sensor a Modulation coil Connection and wiring diagram internal cont 106 Designs 5692 673 GB...
Страница 107: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 107 Designs 5692 673 GB...
Страница 111: ...Parts lists cont 111 Parts lists 5692 673 GB...
Страница 112: ...Parts lists cont 112 Parts lists 5692 673 GB...
Страница 113: ...Parts lists cont 113 Parts lists 5692 673 GB...
Страница 114: ...Parts lists cont 114 Parts lists 5692 673 GB...
Страница 121: ...121 5692 673 GB...
Страница 122: ...122 5692 673 GB...
Страница 123: ...123 5692 673 GB...