External extension H1
The external extension is connected
to the boiler control unit via the KM
BUS. The following functions can be
controlled or processed simulta-
neously via the extension:
A
ON/OFF switch (on site)
sÖ
Heating circuit pump for the
heating circuit without mixer
sA
Cylinder primary pump
sK
DHW circulation pump (only for
weather-compensated opera-
tion)
fÖ
Power supply
gÖ
Central fault message
aVD
&
External blocking
(terminals 2 - 3)
&
External demand
(terminals 1 - 2)
&
External heating program
changeover (terminals 1 - 2)
(only for weather-compen-
sated operation)
The allocation of the function
"External heating program
changeover" is set via coding
address "91".
aVF
External set value 0 to 10 V
aVG
KM BUS
Extensions for external connections . . .
(cont.)
94
Function description
5692
673
GB