94
1432.2 "Operating mode of primary circuit pump"
Setting
Explanations
0
Internal circulation pump is operated with constant dif-
ferential pressure.
1 to 20
Internal circulation pump is operated with rising differ-
ential pressure.
Adjustable from 1 to 20 mbar
1503.0 "Minimum heating output"
Setting
Explanations
A limit can be set on the minimum heating output for
heating mode.
...
Delivered condition specified by settings specific to
the appliance
5 to 100
Adjustable from 5 to 100 %
DHW
Note
Parameter values in
bold
are factory settings.
497.1 "DHW circulation pump for auxiliary function DHW heating"
Setting
Explanations
DHW circulation pump:
OFF
0
OFF during hygiene function
ON
1
ON during hygiene function
Danger
Risk of injury due to increased DHW tempera-
ture.
Inform the system user of the risk from the high-
er outlet temperature at the taps.
497.2 "DHW circulation pump for DHW heating"
Setting
Explanations
DHW circulation pump:
OFF
0
OFF during DHW heating to standard set value
ON
1
ON during DHW heating to standard set value
System configuration (parameters)
Boiler
(cont.)
5853335
Parameter