162
Settings and test values
Set val-
ue
Commis-
sioning
Mainte-
nance/
service
Mainte-
nance/
service
Mainte-
nance/serv-
ice
Date
Signa-
ture
Static pressure
mbar
kPa
≤
30
≤
3.0
Supply pressure (flow pressure)
For natural gas E
For natural gas LL
mbar
kPa
17.4-25
1.74-2.5
Tick gas type.
Carbon dioxide content CO
2
*2
■
At lower heating output
% by
vol.
7.4-9.5
■
At upper heating output
% by
vol.
7.4-9.5
Oxygen content O
2
*3
■
At lower heating output
% by
vol.
4.0-7.6
■
At upper heating output
% by
vol.
4.0-7.6
Carbon monoxide content CO
■
At lower heating output
ppm
< 1000
■
At upper heating output
ppm
< 1000
Fuel cell module
■
Electrical output
W
750
■
Power generated
kWh
■
Amount of gas consumed
m
3
■
Hours run
h
■
Distilled water cartridge replaced
■
Air filter A replaced
■
Air filter B replaced
■
CO sensor replaced
*2
If the fuel cell module is in operation when the measurement is taken, the result may be below the set value.
*3
If the fuel cell module is in operation when the measurement is taken, the result may be above the set value.
Commissioning/service reports
Commissioning/service reports
5853335
Appendix