1431.3 "CO2 factor power exported to grid per kWh"
Setting
Explanations
CO
2
factor in g/kWh
800
Factor in the delivered condition 800 g/kWh
0 to 1000
Adjustable from 0.00 to 10.00
≙
0 to 1000 g/kWh
Subscriber numbers of the connected extensions
All extensions connected to the heat generator must
have a subscriber number. The subscriber number is
set on the rotary switch S1 at each extension.
Fig. 80
Rotary switch S1 settings:
■
Adaptor in cylinder module (electronics module
M2IO, standard delivery):
0
■
Adaptor EM-EA1 (max. 3 extensions in one system)
Consecutive no. (any sequence):
1
up to
3
■
EM-P1 extension
–
If no heating circuits with mixers are available in
the system:
1
–
If heating circuits with mixer (EM-M1 or EM-MX
extensions) are present in the system: Always set
subscriber number EM-P1 extension to consecu-
tive number after extensions EM-M1 or EM-MX.
Note
Extensions EM-EA1 may have the same subscriber
number as the extensions EM-P1, EM-M1 or EM-MX.
The following table shows the possible features of a
system.
Function
Electronics mod-
ule
Extension
Setting
Rotary switch S1
Cylinder module
M2IO
Part of std. delivery
0
Heating circuit 2 with mixer
ADIO
EM-M1/EM-MX
1
Heating circuit 3 with mixer
ADIO
EM-M1/EM-MX
2
Heating circuit 4 with mixer
ADIO
EM-M1/EM-MX
3
Heating circuit 1 without mixer (circulation
pump behind low loss header)
ADIO
EM-P1
4
System configuration (parameters)
Fuel cell
(cont.)
5853335
Parameter