1.
Insert the burner and tighten screws
F
diagonally.
Torque: 6.5 Nm
2.
Fit gas supply pipe
E
with a new gasket.
Torque: 30 Nm
3.
Check the gas connections for leaks.
Danger
Escaping gas leads to a risk of explosion.
Check the fitting for gas tightness.
4.
Connect the cables/leads:
■
Fan motor
A
■
Ionisation electrode
B
■
Ignition unit
C
■
Earth
D
Checking the neutralising system (if installed)
5-yearly maintenance of fuel cell module
Note
Before carrying out the maintenance work:
■
The fuel cell module must be in maintenance mode.
Start maintenance mode, see page 72.
■
The distilled water must have been drained.