119
Control unit
message
System characteristics
Cause
Measures
F.200/1AF0
No power generation
Combustion control CO
content outside tolerance
range
Check gas type setting, correct if
required.
If the correct gas type has been
set, notify Viessmann Technical
Service.
Note
The message can
only
be cleared
on the programming unit of the fuel
cell module.
F.248/67F1
No power generation
Air in the distilled water
circuit
Carry out fuel cell module commis-
sioning again.
If the fault recurs, notify Viessmann
Technical Service.
Note
The message can
only
be cleared
on the programming unit of the fuel
cell module.
F.249/67F9
No power generation
Air in the distilled water
circuit
Carry out fuel cell module commis-
sioning again.
If the fault recurs, notify Viessmann
Technical Service.
Note
The message can
only
be cleared
on the programming unit of the fuel
cell module.
F.294/9BF0
No power generation
Blockage in the flue sys-
tem
Check flue system.
Note
Reset the message on the fuel cell
module programming unit.
Then switch the ON/OFF switch of
the fuel cell module OFF for ap-
prox. 10 s and ON again.
F.296/A8F0
No power generation
Gas pressure too low
Gas supply interrupted
Check the gas supply.
F.297/A9F0
No power generation
Gas pressure too high
Check the gas supply.
F.299
Wrong time
Real-time clock fault
Set the time. Check battery in heat
management unit.
Troubleshooting
Fault messages on the gas condensing…
(cont.)
5853335
Diagnosis