97
Fault code dis-
played
System characteristics
Cause
Measures
db
Control mode without room
influence
Short circuit, room tem-
perature sensor, heating
circuit 2 (with mixer)
Check room temperature sensor,
heating circuit 2
dC
Control mode without room
influence
Short circuit, room tem-
perature sensor, heating
circuit 3 (with mixer)
Check room temperature sensor,
heating circuit 3
dd
Control mode without room
influence
Lead break, room temper-
ature sensor, heating cir-
cuit 1 (without mixer)
Check room temperature sensor
for heating circuit 1 and remote
control configuration (see
page 123)
dE
Control mode without room
influence
Lead break, room temper-
ature sensor, heating cir-
cuit 2 (with mixer)
Check room temperature sensor
for heating circuit 2 and remote
control configuration (see
page 123)
dF
Control mode without room
influence
Lead break, room temper-
ature sensor, heating cir-
cuit 3 (with mixer)
Check room temperature sensor
for heating circuit 3 and remote
control configuration (see
page 123)
E1
Burner in a fault state
Ionisation current too high
during calibration
Check gap between ionisation
electrode and burner gauze as-
sembly (see page 50).
In open flue operation, prevent
high incidence of dust in the com-
bustion air.
Press reset button
R
.
E3
Burner in a fault state
Heat transfer too low dur-
ing calibration.
Temperature limiter has
shut down.
Ensure adequate heat transfer.
Press reset button
R
.
E4
Burner blocked
24 V power supply fault
Replace control unit.
E5
Burner blocked
Flame amplifier fault
Replace control unit.
E6
Burner blocked
System pressure too low
Top up with water.
E7
Burner in a fault state
Ionisation current too low
during calibration
Check ionisation electrode:
■
Distance to burner gauze assem-
bly (see page 50)
■
Electrode contamination
■
Connecting lead and plug-in con-
nections
Check flue system; remedy flue
gas recirculation if required.
Press reset button
R
.
E8
Burner in a fault state
Ionisation current lies out-
side the permissible range
Check gas supply (gas pressure
and gas flow switch), gas train and
connection pipe.
Check assignment of gas type (see
page 43).
Check ionisation electrode:
■
Distance to burner gauze assem-
bly (see page 50)
■
Electrode contamination
Press reset button
R
.
Troubleshooting
Fault codes
(cont.)
5773 238 GB
Diagnosis
Содержание 7513244
Страница 11: ...11 8 9 4x 8x 12 10 11 Fig 2 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 12: ...12 13 14 15 Fig 3 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 13: ...13 16 Fig 4 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 14: ...14 sF 17 19 21 20 18 Fig 5 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 15: ...15 24 22 23 Fig 6 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 16: ...16 27 26 25 Fig 7 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 35: ...35 2x 1 4 2 3 5 Fig 27 Installation sequence Fitting the front panels 5773 238 GB Installation ...
Страница 135: ...135 Parts lists Hydraulic assembly 5773 238 GB Components ...
Страница 146: ...146 0004 0002 0005 0006 0001 0003 Fig 107 Parts lists Miscellaneous 5773 238 GB Components ...