95
Fault code dis-
played
System characteristics
Cause
Measures
9E
Control mode
No flow rate in solar circuit
or flow rate too low, or
temperature limiter has
triggered.
Check solar circuit.
Acknowledge fault message (see
separate installation and service
instructions).
9F
Control mode
Solar control module fault
Replace solar control module
A2
Emergency mode with insuffi-
cient system pressure
System pressure too low
Top up with water
A4
Control mode
Max. system pressure ex-
ceeded
Check the system pressure.
Check the function and sizing of
the expansion vessel.
Vent the heating system.
Coding address "0E" is set to "1" to
document the fault. Must be man-
ually reset to "0" after troubleshoot-
ing.
A7
Control mode as per deliv-
ered condition
Programming unit faulty
Replace programming unit
A8
Burner blocked. The venting
program is started automati-
cally (see page 68)
Air in the internal circula-
tion pump or minimum
flow rate not achieved
Vent the system if the fault mes-
sage continues to be displayed
A9
If a heating circuit with mixer
is connected, the burner op-
erates at its lower heating
output.
If only one heating circuit
without mixer is connected,
the burner is blocked.
Internal circulation pump
blocked
Check the circulation pump
b0
Burner blocked
Short circuit, flue gas tem-
perature sensor
Check the flue gas temperature
sensor
b1
Control mode as per deliv-
ered condition
Communication error, pro-
gramming unit
Check connections and replace
programming unit if required
b4
Regulates as if the outside
temperature were 0 °C
Internal fault
Replace the control unit
b5
Control mode as per deliv-
ered condition
Internal fault
Replace the control unit
b7
Burner blocked
Fault, boiler coding card
Plug in or replace boiler coding
card
b8
Burner blocked
Lead break, flue gas tem-
perature sensor
Check the flue gas temperature
sensor
bA
Mixer regulates to 20 °C flow
temperature.
Communication error, ex-
tension kit for heating cir-
cuit 2 (with mixer)
Check the extension kit connec-
tions and coding
bb
Mixer regulates to 20 °C flow
temperature.
Communication error, ex-
tension kit for heating cir-
cuit 3 (with mixer)
Check the extension kit connec-
tions and coding
bC
Control mode without remote
control
Communication error,
Vitotrol remote control,
heating circuit 1 (without
mixer)
Check connections, cable and cod-
ing address "A0" in group
"Heat-
ing circuit"
, and check remote
control configuration (see
page 123).
For wireless remote controls:
Check connection, place remote
control unit close to the boiler.
Troubleshooting
Fault codes
(cont.)
5773 238 GB
Diagnosis
Содержание 7513244
Страница 11: ...11 8 9 4x 8x 12 10 11 Fig 2 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 12: ...12 13 14 15 Fig 3 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 13: ...13 16 Fig 4 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 14: ...14 sF 17 19 21 20 18 Fig 5 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 15: ...15 24 22 23 Fig 6 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 16: ...16 27 26 25 Fig 7 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 35: ...35 2x 1 4 2 3 5 Fig 27 Installation sequence Fitting the front panels 5773 238 GB Installation ...
Страница 135: ...135 Parts lists Hydraulic assembly 5773 238 GB Components ...
Страница 146: ...146 0004 0002 0005 0006 0001 0003 Fig 107 Parts lists Miscellaneous 5773 238 GB Components ...