86
Parameter address
b5:...
With heating circuit pump logic function:
Heating circuit pump "OFF"
Heating circuit pump "ON"
3
RT
actual
>
RT
set
+ 3 K
RT
actual
< RT
set
+ 2 K
4
RT
actual
>
RT
set
+ 2 K
RT
actual
< RT
set
+ 1 K
5
RT
actual
>
RT
set
+ 1 K
RT
actual
< RT
set
6
RT
actual
>
RT
set
RT
actual
< RT
set
–
1 K
7
RT
actual
>
RT
set
–
1 K
RT
actual
< RT
set
–
2 K
8
RT
actual
>
RT
set
–
2 K
RT
actual
< RT
set
–
3 K
Coding in the delivered condition
Possible change
C5:20
Electronic minimum flow tempera-
ture limit 20 °C (only for operation
with standard room temperature)
C5:1
to
C5:127
Minimum limit adjustable from 1 to
127 °C (limited by boiler-specific pa-
rameters)
C6:74
Electronic maximum flow tempera-
ture limit 74 °C (only for weather-
compensated control units)
C6:10
to
C6:127
Maximum limit adjustable from 10 to
127 °C (limited by boiler-specific pa-
rameters)
d3:14
Heating curve slope = 1.4
d3:2
to
d3:35
Heating curve slope adjustable from
0.2 to 3.5 (see page 64)
d4:0
Heating curve level = 0
d4:–13
to
d4:40
Heating curve level adjustable from
–
d5:0
With external heating program
changeover (observe setting for
coding addresses "3A", "3b" and
"3C" in the
"General"
group).
Heating program switches to "Con-
stant central heating with reduced
room temperature" or "Standby
mode" (subject to the value selec-
ted for the set reduced room tem-
perature).
d5:1
Heating program switches to "Con-
stant operation with standard room
temperature".
d6:0
Heating circuit pump stays in con-
trol mode at signal "External block-
ing"
d6:1
Heating circuit pump stops at "Exter-
nal blocking" signal (subject to cod-
ing addresses "3A", "3b" and "3C")
d6:2
Heating circuit pump starts at "Exter-
nal blocking" signal (subject to cod-
ing addresses "3A", "3b" and "3C")
d7:0
Heating circuit pump stays in con-
trol mode at signal "External de-
mand"
d7:1
Heating circuit pump stops at "Exter-
nal demand" signal (subject to cod-
ing addresses "3A", "3b" and "3C")
d7:2
Heating circuit pump starts at "Exter-
nal demand" signal (subject to cod-
ing addresses "3A", "3b" and "3C")
d8:0
With EA1 extension:
No operating program changeover.
d8:1
Operating program changeover via
input DE1.
d8:2
Operating program changeover via
input DE2.
d8:3
Operating program changeover via
input DE3.
E1:1
Do not adjust
E2:50
With remote control:
E2:0
to
Display correction
–
5 K
to
Code 2
"Heating circuit ..."
(cont.)
5773 238 GB
Codes
Содержание 7513244
Страница 11: ...11 8 9 4x 8x 12 10 11 Fig 2 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 12: ...12 13 14 15 Fig 3 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 13: ...13 16 Fig 4 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 14: ...14 sF 17 19 21 20 18 Fig 5 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 15: ...15 24 22 23 Fig 6 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 16: ...16 27 26 25 Fig 7 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 35: ...35 2x 1 4 2 3 5 Fig 27 Installation sequence Fitting the front panels 5773 238 GB Installation ...
Страница 135: ...135 Parts lists Hydraulic assembly 5773 238 GB Components ...
Страница 146: ...146 0004 0002 0005 0006 0001 0003 Fig 107 Parts lists Miscellaneous 5773 238 GB Components ...