49
P 82
ECO automatics passive/active
ECO function image.
Value 0 – passive (the function is not active it means heating isn’t blocked)
Value 1 – active (the function is active it means heating is blocked)
P 83
Summer/winter temperature
[
o
C]
Setting the outside temperature at which the heating circuit requirement will be ignored.
Note: The evaluation on the basis of average outside temperatures.
P 84
Summer/winter constant
[h]
By setting this value we determine the time for calculation of average outside temperature in
connection with line no. 83.
P 85
Summer/winter current status
Summer/winter current status image.
Value 0 – winter (the function is not active it means heating isn’t blocked)
Value 1 – summer (the function is active it means heating is blocked)
P 86
Heating system
Setting the type of heating bodies.
Value 0 – floor heating
Value 1 – convectors
Value 2 – plate radiators
Value 3 – cast iron radiators
P 87
HC antifreeze protection off/on
Setting the heating circuit antifreeze protection on the basis of outside temperature
If the outside temperature is+1,5
o
C and higher the heating circuit pump only will slow down after the
requirement for heating has ceased.
If the outside temperature is in the range from +1,5 to -4
o
C the heating circuit pump will be switched
on every 6 hours for the period of 10 minutes.
If the outside temperature is in the range from -4
o
C and lower the heating circuit pump will be
permanently switched on.
Pump switch-off hysteresis is 0,5
o
C.
Value 0 – function isn’t active
Value 1 – function is active
Keeping the function activated is recommended by the manufacturer.
P 88
Servo overrun time
[s]
This value depends on the used three-way mixing valve of the heating branch and it is taken from the
catalogue sheet. If you use three-way valve SQK 34 then the correct value is already set.
P 100
Setting the day of time schedule for HC
Setting the day of week required for setting the individual heating periods
Value 1 - 7 – corresponds to the days from Monday to Sunday, we set it separately every day
Value 0 – setting all days at once
P 101
First HC period switched on
[h:min.]
Setting the time of switching-on the first period for HC heating
Note: It isn’t necessary to use the second and third period
P 102
First HC period switched off
[h:min.]
Setting the switching-off time of the first period for HC heating
P 103
Desired space temperature in the first period
[
o
C]
Setting the desired space temperature in the first HC period
P 104
Second HC period switched on
[h:min.]
Setting the switching-on time of the second period for HC heating
P 105
Second HC period switched off
[h:min.]
Setting the switching-off time of the second period for HC heating
P 106
Desired space temperature in the second period
[
o
C]
Setting the desired space temperature in the second HC period
P 107
Third HC period switched on
[h:min.]
Setting the switching-on time of the third period for HC heating
P 108
Third period HC switched off
[h:min.]
Setting the switching-off time of the third period for HC heating