42
Parameter
Description
Units
Set by the
manufacturer
Range
Resolution
P 111
Desired space temperature in attenuation
[
o
C]
19
5 … 25
0,1
P 120
Setting the day of time schedule for HW
1
0 … 7
1
P 121
First period HW switched on
[h:min.]
6:00
0:00 … 23:59
1 min.
P 122
First period HW switched off
[h:min.]
22:00
0:00 … 23:59
1 min.
P 123
Desired temperature HW in the first period
[
o
C]
60
10 … 65
1
P 124
Second period HW switched on
[h:min.]
23:59
0:00 … 23:59
1 min.
P 125
Second period HW switched off
[h:min.]
23:59
0:00 … 23:59
1 min.
P 126
Desired temperature HW in the second
period
[
o
C]
55
10 … 65
1
P 127
Third period HW switched on
[h:min.]
23:59
0:00 … 23:59
1 min.
P 128
Third period HW switched off
[h:min.]
23:59
0:00 … 23:59
1 min.
P 129
Desired temperature HW in the third period
[
o
C]
50
10 … 65
1
P 130
Hysteresis HW
[
o
C]
4
1 … 10
1
P 131
Time schedule reset HW
0
0 … 1
1
P 140
Feeder runtime
[s]
5
3 … 10
0,1
P 150
Feeder X1 lignite
[%]
0
0
0
P 151
Feeder Y1 lignite – 4 sect.
[s]
77
55 … 95
1
Feeder Y1 lignite – 5 sect.
[s]
68
50 … 95
1
Feeder Y1 lignite – 6 sect.
[s]
47
30 … 80
1
Feeder Y1 lignite – 7 sect.
[s]
45
25 … 75
1
P 152
Feeder X2 lignite
[%]
33
33
0
P 153
Feeder Y2 lignite – 4 sect.
[s]
41
28 … 65
1
Feeder Y2 lignite – 5 sect.
[s]
38
20 … 70
1
Feeder Y2 lignite – 6 sect.
[s]
26
15 … 60
1
Feeder Y2 lignite – 7 sect.
[s]
23
12 … 50
1
P 154
Feeder X3 lignite
[%]
66
66
0
P 155
Feeder Y3 lignite – 4 sect.
[s]
27
21 … 55
1
Feeder Y3 lignite – 5 sect.
[s]
25
10 … 55
1
Feeder Y3 lignite – 6 sect.
[s]
18
5 … 55
1
Feeder Y3 lignite – 7 sect.
[s]
15
5 … 50
1
P 156
Feeder X4 lignite
[%]
100
100
0
P 157
Feeder Y4 lignite – 4 sect.
[s]
19
15 … 45
1
Feeder Y4 lignite – 5 sect.
[s]
15
5 … 45
1
Feeder Y4 lignite – 6 sect.
[s]
12
5 … 45
1
Feeder Y4 lignite – 7 sect.
[s]
10
5 … 45
1
P 158
Feeder runtime in the attenuation – lignite
[s]
10
3 … 20
1
P 159
Standstill time(delay) feeder in the
attenuation – lignite
[min]
40
10 … 240
1
P 160
Ventilator X1 lignite
[%]
0
0
0
P 161
Ventilator Y1 lignite – 4 sect.
[%]
26
15 … 45
1
Ventilator Y1 lignite – 5 sect.
[%]
27
15 … 50
1
Ventilator Y1 lignite – 6 sect.
[%]
26
15 … 50
1
Ventilator Y1 lignite – 7 sect.
[%]
35
15 … 60
1
P 162
Ventilator X2 lignite
[%]
33
33
0
P 163
Ventilator Y2 lignite – 4 sect.
[%]
33
25 … 50
1
Ventilator Y2 lignite – 5 sect.
[%]
32
20 … 50
1
Ventilator Y2 lignite – 6 sect.
[%]
31
20 … 55
1
Ventilator Y2 lignite – 7 sect.
[%]
43
20 … 70
1
P 164
Ventilator X3 lignite
[%]
66
66
0
P 165
Ventilator Y3 lignite – 4 sect.
[%]
40
25 … 68
1
Ventilator Y3 lignite – 5 sect.
[%]
39
25 … 70
1
Ventilator Y3 lignite – 6 sect.
[%]
38
25 … 75
1
Ventilator Y3 lignite – 7 sect.
[%]
63
25 … 90
1
P 166
Ventilator X4 lignite
[%]
100
100
0
P 167
Ventilator Y4 lignite – 4 sect.
[%]
52
40 … 70
1
Ventilator Y4 lignite – 5 sect.
[%]
48
30 … 80
1
Ventilator Y4 lignite – 6 sect.
[%]
47
30 … 85
1
Ventilator Y4 lignite – 7 sect.
[%]
78
30 … 95
1
P 168
Ventilator slowing-down in the attenuation
regime– lignite
[s]
90
5 … 200
1
P 169
Ventilator output in the attenuation – lignite
[%]
50
10 … 100
1
P 170
Feeder X1 hard coal
[%]
0