Module
Allowable Total CAN Cable Length, ft (m)
Liebert XDV8
580 (177)
Liebert XDV10
580 (177)
Liebert XDO16
590 (180)
Liebert XDO20
590 (180)
Liebert XDH20
580 (177)
Liebert XDH32
585 (178)
*The internal CANbus cable within the Liebert XD module and the remote sensors has been accounted for.
Table 3.22 Allowable total CAN cable length
Figure 3.32 Single daisy chain of Liebert XDO smart modules in CANbus network
Cable
Segments
Length of Each ft. (m)
Cumulative Length ft. (m)
14
6 (1.8)
84 (25.6)
1
20 (6)
20 (6)
1
30 (9.1)
30 (9.1)
Combined cable length
134 (40.8)
Table 3.23 Cumulative cable length in Figure 3.32 above
The cumulative length of cable used in the example in Figure 3.32 above is 134 ft. (40.8m), far shorter
than the maximum allowable cable run of 580 ft. (177m) for Liebert XDV10 modules.
3.27.3 Remote Sensor Placement Within the CANbus
Two remote sensors are shipped with the Liebert XDP. One shielded CANbus cable is provided with each
sensor. Sensor A is to be connected to the directly the Liebert XDP. Sensor B is to be connected to the
CANbus within the smart module chain. This can be at the end of the chain as shown in Figure 3.33 on
the facing page. For proper placement within the room, see
Temperature/Humidity Sensor Locations
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
62
Содержание Liebert XD Series
Страница 1: ...Liebert Xtreme Density System Design Manual...
Страница 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Страница 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Страница 45: ...Figure 3 22 Liebert XD return header orientation Vertiv Liebert Xtreme Density System Design Manual 45...
Страница 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Страница 76: ...Figure 4 12 Liebert XDO internal mounting location Vertiv Liebert Xtreme Density System Design Manual 76...
Страница 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Страница 90: ...Figure 4 23 Suspending single Liebert XDV from Unistruts Vertiv Liebert Xtreme Density System Design Manual 90...
Страница 103: ...Figure 5 4 Piping locations floor stand and valve assembly Vertiv Liebert Xtreme Density System Design Manual 103...
Страница 112: ...Figure 5 16 Front view of Liebert XDP and electrical enclosure Vertiv Liebert Xtreme Density System Design Manual 112...
Страница 115: ...Figure 5 19 Liebert XDP high voltage connections 60Hz Vertiv Liebert Xtreme Density System Design Manual 115...
Страница 116: ...Figure 5 20 Liebert XDP high voltage connections 50Hz Vertiv Liebert Xtreme Density System Design Manual 116...
Страница 120: ...Figure 6 2 Condenser planning dimensional data Six fan units Vertiv Liebert Xtreme Density System Design Manual 120...
Страница 121: ...Figure 6 3 Typical condenser footprint dimensions Vertiv Liebert Xtreme Density System Design Manual 121...
Страница 138: ...Figure 6 13 Drycooler planning dimensional data Eight fan units Vertiv Liebert Xtreme Density System Design Manual 138...
Страница 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Страница 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Страница 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Страница 170: ...Figure 7 11 CAN Isolator location within the Liebert XDP XDC Vertiv Liebert Xtreme Density System Design Manual 170...
Страница 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Страница 198: ...Figure 9 7 Liebert XDP model number nomenclature Vertiv Liebert Xtreme Density System Design Manual 198...
Страница 199: ......